Motor hums but won't start to turn
On start the motor hums or buzzes but won't rotate — it may draw heavy current and trip protection. Often a sign it's only getting two phases or is mechanically locked.
Safety first
A humming, non-turning motor draws locked-rotor current and overheats fast. Don't leave it energised. A seized load can release suddenly — keep clear.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Single-phasing (lost one phase)
Most likelyWith only two phases, a three-phase motor can't develop starting torque — it hums and overheats.
- 2
Mechanically jammed or seized load
#2A seized bearing or jammed driven machine stops the rotor turning even with full supply.
- 3
Failed start capacitor (single-phase motors)
#3On single-phase motors, a dead start capacitor leaves the motor humming with no starting torque.
- 4
Motor winding fault
Least likelyAn open or shorted winding can leave the motor unable to start while still drawing current.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeIsolate immediately if humming. Then, on a brief controlled attempt, check all three phase-to-phase voltages at the motor.
Three balanced phase-to-phase voltages at the motor.
All phases present — suspect a mechanical jam, capacitor, or winding.
A missing phase explains the hum — chase the single-phasing.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Motor hums, won't turn
→ step 2 - 2decision
Are all three phases present at the motor?
Yes→ step 3No→ step 4 - 3decision
Does the shaft turn freely by hand?
Yes→ step 5No→ step 6 - 4result
Single-phasing — chase the lost phase.
- 5result
Test start capacitor (1ph) or windings (3ph) — repair/replace.
- 6result
Seized/jammed load — hand to mechanical.
Common mistakes apprentices make
- Leaving the motor humming and letting it cook on locked-rotor current.
- Not checking for a lost phase before blaming the motor.
- Forgetting the start capacitor on single-phase motors.
- Failing to uncouple the load to separate a jam from a motor fault.
When to stop & escalate
A confirmed single-phase supply fault goes upstream; a seized driven machine goes to mechanical; a faulty winding means a motor repair/rewind.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
Three-phase equipment single-phasing (lost a phase)
Three-phase equipment is misbehaving — motors humming, struggling, overheating, or tripping — because one phase has been lost somewhere between the supply and the load.
Motor overload keeps tripping
The thermal/electronic overload trips repeatedly, either on start or after the motor has run for a while. Resetting only buys you a short run before it trips again.
Motor won't start and makes no sound at all
Press start and nothing happens — no hum, no movement, no attempt to turn. The motor is completely dead rather than struggling.
Learn the theory
How the gear and circuits behind this fault actually work.
Induction motor
The workhorse AC motor — a rotating magnetic field in the stator drags the rotor around with it.
Single-phasing
What happens when a three-phase load loses one phase — and why it's so damaging to motors.
Motor slip & torque-speed
Why an induction motor must run slightly slower than its field, and how its torque changes from start to full speed.