Device

RCD (safety switch)

Detects earth leakage and disconnects fast to protect people from electric shock.

ANtrip coiltestcircuitsensing toroidleakage to earthtrips main contacts
RCD — a sensing toroid detects active/neutral imbalance and trips the main contacts

What it is

An RCD (called a safety switch in homes) protects people against electric shock by detecting current leaking to earth and disconnecting in a fraction of a second.

How it works

The active and neutral conductors pass through a sensing ring (toroid). In a healthy circuit, the current going out (active) equals the current coming back (neutral), so their magnetic effects cancel.

If some current leaks to earth — through a fault or a person — the active and neutral no longer balance. The imbalance induces a current in the sensing coil, which trips the RCD. It's detecting the leakage, not the total load.

Where it's used

Protecting socket and lighting circuits, wet areas, and outdoor circuits. An RCBO combines this earth-leakage protection with overload/short-circuit protection in one device.

Never bypass an RCD to stop nuisance tripping — it's protecting against a shock risk. Trips come from real leakage, cumulative leakage from electronics, moisture, or neutral-earth faults.

What it looks like when it fails

Random or repeat tripping is usually the circuit, not the device: cumulative leakage from a board full of electronics, moisture in a fitting or buried joint, a neutral–earth fault downstream, or one failing appliance. Trips that follow rain, or only when a particular load switches on, are telling you where to look.

The device fails too: it won't reset with everything disconnected (worn mechanism — or a hard N–E fault still present), or the test button does nothing. An RCD that won't trip on its own test button gets replaced, not excused.

How to test it

The test button only proves the mechanism moves — it says nothing about trip current or speed. A proper check needs an RCD tester: it should hold at half rated residual current and trip at rated current (30 mA for personal protection) within the time limits in AS/NZS 3017 — verify the exact limits you test to. A ramp test tells you the actual trip point.

Chasing nuisance trips: unplug everything on the circuit, reset, then reintroduce loads one at a time. A leakage clamp around active and neutral together reads the standing leakage directly — see how much of the trip threshold is already spent before anything 'faults'.

Gotchas

A neutral–earth fault trips RCDs with every load unplugged — that leakage path doesn't need an appliance connected. And leakage adds up: a circuit full of switch-mode supplies and EMC filters can idle close enough to the threshold that one more device tips it over.

Type matters: a standard Type AC can be blinded by the DC-component leakage from VSDs, EV chargers and some inverters — those need Type A or B (the equipment manual says which). And shared or borrowed neutrals between circuits cause 'impossible' trips on the wrong RCD.

Safety first

RCD trips indicate earth leakage — a shock risk. Never defeat or bypass one; find the leakage. Test it operates using its test button periodically.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Related faults

Related definitions