QualifiedHigh risk

RCD trips the moment a specific load is switched on

The RCD is fine until a particular appliance/circuit is switched on, then it trips immediately — clearly pointing at that load or its switch-on behaviour.

Safety first

A load that instantly trips the RCD likely has an earth fault — a shock risk. Isolate it and test before using. Don't bypass the RCD to keep using the appliance.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Earth fault in the appliance

    Most likely

    The appliance has a fault to earth that draws leakage the instant it's energised.

  2. 2

    Heating element / motor winding leakage

    #2

    An element or winding leaking to earth trips the RCD on switch-on.

  3. 3

    High switch-on inrush/filter leakage

    #3

    Some equipment has a switch-on earth-current transient (filters) that trips a sensitive RCD.

  4. 4

    Damaged flex/connection on that load

    Least likely

    A damaged lead or connection on the appliance leaks to earth when live.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Confirm it's that specific load by switching it in isolation and watching the RCD.

Expected reading

RCD trips reliably only when that load is switched on.

If it passes

Confirmed culprit — isolate it and test the appliance.

If it fails

If other loads also trip it, treat as a broader leakage issue.

View all expected readings at once
1. Confirm it's that specific load by switching it in isolation and watching the RCD.
RCD trips reliably only when that load is switched on.
2. Isolate the appliance and insulation-test it (and its flex) to earth.
High insulation resistance to earth.
3. If insulation is good, assess switch-on transient/filter leakage and the RCD's suitability/sensitivity.
Transient within what the RCD should tolerate.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    RCD trips on a specific load

    → step 2
  2. 2
    decision

    Does only that load trip it (in isolation)?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the appliance/flex insulation to earth healthy?

    Yes→ step 5No→ step 6
  4. 4
    result

    Other loads trip it too — treat as a broader leakage issue.

  5. 5
    result

    Suspect switch-on transient/filter leakage — review RCD type/arrangement.

  6. 6
    result

    Earth fault in appliance/element/winding — repair/replace.

Common mistakes apprentices make

  • Continuing to use an appliance that trips the RCD by bypassing protection.
  • Not insulation-testing the appliance and its flex.
  • Assuming nuisance when there's a genuine earth fault.
  • Overlooking a damaged lead on that specific load.

When to stop & escalate

An appliance with an earth fault must be repaired or taken out of use — not run on a defeated RCD. Transient/filter issues with sensitive RCDs may need an RCD-type review.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults