QualifiedHigh risk

RCD / RCBO keeps tripping

An RCD or RCBO trips repeatedly — immediately on reset, randomly during the day, or only when certain equipment runs. The earth-leakage protection is doing its job; something is leaking.

Safety first

An RCD trips because of earth leakage — a real shock risk. Don't defeat it or keep forcing it on. Find the leakage; treat any circuit it protects as potentially faulty.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    A genuine earth-leakage fault on a connected circuit/appliance

    Most likely

    Damaged insulation, a faulty heating element, moisture ingress, or a failing appliance is leaking current to earth.

  2. 2

    Accumulated leakage from many devices on one RCD

    #2

    Lots of electronics/filters each contribute a small standing leakage; together they can push a sensitive RCD over its threshold, especially at switch-on.

  3. 3

    A neutral-earth fault or shared/borrowed neutral

    #3

    A neutral touching earth, or neutrals shared between circuits, creates leakage paths that trip the RCD.

  4. 4

    Moisture or water ingress

    #4

    Water in fittings, outdoor sockets, or junctions creates a leakage path that often appears after rain or wash-down.

  5. 5

    Faulty RCD itself

    Least likely

    Less common, but a worn or faulty RCD can become over-sensitive or nuisance-trip. Prove the leakage is real before blaming the device.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 4
1

Note the pattern: trips instantly on reset, randomly, or only when specific equipment runs? Record what's connected.

Expected reading

A pattern that points at a circuit or appliance (e.g. only trips when the kettle/heater/pump runs).

If it passes

A clear trigger narrows it to one circuit/appliance — isolate that and confirm.

If it fails

If it trips with everything off, suspect wiring (neutral-earth) or the RCD itself.

Mark this test
View all expected readings at once
1. Note the pattern: trips instantly on reset, randomly, or only when specific equipment runs? Record what's connected.
A pattern that points at a circuit or appliance (e.g. only trips when the kettle/heater/pump runs).
2. Safely split the load: turn off / unplug downstream circuits and appliances, reset, then reintroduce them one at a time.
The RCD holds with everything off and trips when the faulty circuit/appliance is reconnected.
3. On the suspect circuit, isolate and carry out insulation resistance testing to earth per your procedure (including checking for neutral-earth faults).
Insulation resistance well above the minimum your procedure allows, with no neutral-earth path.
4. If wiring tests good, consider total standing leakage vs the RCD rating, and verify the RCD itself with the test button / a proper RCD test per procedure.
Standing leakage comfortably below the RCD's threshold and the RCD tripping within spec on test.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    RCD/RCBO keeps tripping

    → step 2
  2. 2
    decision

    Does a specific circuit/appliance trigger the trip?

    Yes→ step 3No→ step 4
  3. 3
    result

    Isolate that circuit/appliance and insulation-test it. Repair the leakage.

  4. 4
    decision

    With all load split off, does it still trip?

    Yes→ step 5No→ step 6
  5. 5
    decision

    Does fixed-wiring insulation test good (no neutral-earth fault)?

    Yes→ step 7No→ step 8
  6. 6
    result

    Likely cumulative leakage — reintroduce loads one at a time; consider splitting across more RCDs.

  7. 7
    result

    Verify the RCD itself; if it operates out of spec, replace it.

  8. 8
    result

    Insulation/neutral-earth fault in the wiring — repair and retest.

Common mistakes apprentices make

  • Strapping out or replacing the RCD with a non-RCD device to 'fix' the tripping — that removes vital protection.
  • Not splitting the load to localise the fault before testing everything at once.
  • Forgetting neutral-earth faults and shared neutrals as a leakage source.
  • Blaming the RCD before proving the leakage isn't real.

When to stop & escalate

Confirmed insulation faults in fixed wiring should be repaired by a qualified person and the circuit retested. Persistent cumulative-leakage problems may need the installation's RCD arrangement reviewed. Always follow local wiring rules and site procedures — never remove earth-leakage protection as a workaround.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.