Device

Induction motor

The workhorse AC motor — a rotating magnetic field in the stator drags the rotor around with it.

What it is

An induction motor converts electrical energy into rotation. It has a stationary part (the stator, with windings) and a rotating part (the rotor). It's robust, cheap, and everywhere.

How it works

Three-phase current in the stator windings creates a magnetic field that rotates around the stator. This moving field induces currents in the rotor, which create their own field — and the rotor is dragged along, chasing the rotating field.

The rotor always runs slightly slower than the field (that difference is 'slip'), which is what lets it induce rotor current and produce torque. Single-phase motors need a start winding/capacitor to get the field rotating in the first place.

Where it's used

Pumps, fans, compressors, conveyors, machine tools — almost any rotating load. Direction reverses by swapping any two of the three phases.

Common faults: won't start (no supply, single-phasing, seized load), runs hot (overload, cooling, imbalance), tripping overloads, bearing noise, and low insulation to earth.

What it looks like when it fails

Windings fail three ways: open (one phase reads OL — the motor hums or won't start), shorted turns (runs hot, draws unbalanced current, trips the overload), or broken down to earth (trips the RCD or breaker; megger reads low). Single-phasing looks like a winding fault but usually starts upstream — a blown fuse, a burnt contactor pole, a loose termination.

Mechanically, bearings dry out and rumble before they seize — and a seized or jammed load trips on locked-rotor current with a perfectly good motor on the end of it. Blocked fan cowls cook motors slowly.

How to test it

Isolated and proven dead, at the motor terminals: winding resistance between each phase pair should be low and near-identical — the balance between pairs matters more than the exact number (a few ohms on small motors, less as they get bigger). One pair reading OL is an open winding; one pair noticeably lower than the others suggests shorted turns.

Insulation resistance: 500 V DC megger from each winding to earth — commonly expected to be well above 1 MΩ (verify the acceptance value you work to; a damp or dirty motor reads low and may recover after drying out). Running: clamp each phase — currents should be close to balanced, at or under nameplate FLC.

Gotchas

Disconnect the VSD or soft starter before you megger — 500 V into drive electronics kills them. Same goes for thermistor/PTC sensor leads: insulation-test the power windings only, never the sensor circuit.

On six-terminal motors, note the link arrangement (star or delta) before measuring or you'll misread the winding resistance. A motor that megs fine cold can still break down hot or damp — test as found where you can. And on dual-voltage nameplates, use the FLC for the connection you actually have.

Safety first

Rotating machinery can start unexpectedly when protection resets. Isolate, lock off, and prove dead; allow hot motors to cool.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Related faults

Related definitions