AdvancedHigh risk

Sub-main keeps tripping the main board

A sub-board's incoming protective device (or the main feeding it) trips — taking out everything downstream — and you need to tell overload from a fault on the sub-main or sub-board.

Safety first

Sub-mains carry significant current. Isolate and prove dead; a sub-main fault can be high-energy. Licensed electrical work.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Downstream fault on a sub-board circuit

    Most likely

    A short/earth fault on one of the sub-board's circuits trips the sub-board incomer or the main.

  2. 2

    Sub-board overloaded

    #2

    Total sub-board load exceeds the sub-main/incomer rating, tripping after running.

  3. 3

    Sub-main cable fault

    #3

    Damage, moisture, or rodent damage to the sub-main cable itself.

  4. 4

    Discrimination / coordination issue

    Least likely

    Protective devices not coordinated, so an upstream device trips before the downstream one.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Note when it trips (instantly vs after load) and isolate the sub-board's circuits, then restore to localise.

Expected reading

Sub-main holds with the sub-board circuits isolated.

If it passes

Restore circuits one at a time — the one that drops it has the fault.

If it fails

Trips with all sub-board circuits off — suspect the sub-main cable or overload.

View all expected readings at once
1. Note when it trips (instantly vs after load) and isolate the sub-board's circuits, then restore to localise.
Sub-main holds with the sub-board circuits isolated.
2. If it holds with circuits off, reintroduce them to find the faulty/overloading circuit.
The circuit that drops the feed identified.
3. If it trips with the sub-board isolated, test the sub-main cable and check device coordination.
Sound sub-main cable and coordinated protection.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Sub-main keeps tripping

    → step 2
  2. 2
    decision

    Does the feed hold with the sub-board circuits isolated?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Reintroducing circuits, does one drop the feed?

    Yes→ step 5No→ step 6
  4. 4
    result

    Trips with all off — test the sub-main cable / check overload.

  5. 5
    result

    That circuit has the fault — rectify it.

  6. 6
    result

    No single circuit — sub-board overloaded; review the load.

Common mistakes apprentices make

  • Resetting the feed repeatedly into a downstream fault.
  • Not isolating the sub-board to separate the cable from the load.
  • Overlooking a discrimination/coordination problem.
  • Upsizing the incomer instead of finding the fault.

When to stop & escalate

Sub-main cable faults and protection coordination are licensed (and sometimes design) work. A genuinely overloaded sub-board needs a load/sizing review before any rating change.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.