QualifiedHigh risk

MCB (circuit breaker) keeps tripping

A circuit breaker trips repeatedly — instantly on reset, or after a load runs for a while — and you need to tell a short from an overload from a faulty breaker.

Safety first

A tripping breaker is protecting against a real fault current. Don't keep resetting into a short or upsize the breaker. Isolate and investigate.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Short circuit (instant trip)

    Most likely

    A short trips the breaker's magnetic (instantaneous) element the moment it's energised.

  2. 2

    Overload (trips after running)

    #2

    Sustained current above rating trips the thermal element after a delay.

  3. 3

    Earth fault on the circuit

    #3

    An earth fault can draw enough current to trip an MCB (and any RCD).

  4. 4

    Wrong breaker rating/characteristic

    #4

    An under-rated breaker or wrong curve trips on normal load/inrush.

  5. 5

    Faulty breaker

    Least likely

    An aged or faulty breaker can trip below its rating.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Note when it trips: instantly on reset (short), after a delay/under load (overload).

Expected reading

A pattern separating short from overload.

If it passes

Instant → short; delayed → overload. Proceed accordingly.

If it fails

If random, suspect an intermittent fault or a faulty breaker.

View all expected readings at once
1. Note when it trips: instantly on reset (short), after a delay/under load (overload).
A pattern separating short from overload.
2. For an instant trip, isolate and test the circuit/wiring for a short or earth fault per procedure.
No short or earth fault on the circuit.
3. For a delayed trip, measure the load current against the breaker rating and confirm the rating/curve suits the circuit.
Load within rating and an appropriate breaker rating/curve.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    MCB keeps tripping

    → step 2
  2. 2
    decision

    Does it trip instantly on reset (vs after a delay)?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the circuit free of shorts/earth faults?

    Yes→ step 4No→ step 5
  4. 4
    decision

    Is load within rating with the correct breaker?

    Yes→ step 6No→ step 7
  5. 5
    result

    Short/earth fault — locate and repair before re-energising.

  6. 6
    result

    Suspect a faulty breaker — replace and re-test.

  7. 7
    result

    Overload or wrong breaker — reduce load / fit correct breaker.

Common mistakes apprentices make

  • Repeatedly resetting into a short.
  • Upsizing the breaker to stop tripping instead of fixing the fault.
  • Not distinguishing instant (short) from delayed (overload) trips.
  • Overlooking an earth fault as the trip source.

When to stop & escalate

A confirmed short or earth fault needs a qualified repair and retest before re-energising. Never fit a larger breaker to defeat protection; rating changes must suit the circuit's design.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.