QualifiedHigh risk

No power to a shed or outbuilding

A shed or outbuilding has lost power — points at the sub-circuit/sub-board feeding it, the submain, a tripped protective device, or moisture.

Safety first

Isolate and prove dead. Outbuildings often have their own sub-board and a submain — confirm what's live. Damp outbuildings increase shock risk.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Protective device feeding the shed tripped/off

    Most likely

    The breaker/RCD at the main board (or the shed's sub-board) has tripped or is off.

  2. 2

    Submain fault

    #2

    The cable feeding the outbuilding has a fault (damage, moisture, rodents).

  3. 3

    Moisture/earth fault tripping protection

    #3

    Damp in the shed wiring or fittings trips the safety switch.

  4. 4

    Sub-board fault

    Least likely

    A fault at the shed's own sub-board/devices.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 2
1

Check the protective device feeding the shed at the main board (and the shed sub-board) for a trip/off.

Expected reading

Devices on; nothing tripped.

If it passes

Not tripped — check the submain and shed wiring for supply/faults.

If it fails

Tripped/off — find why before resetting (don't just re-trip).

View all expected readings at once
1. Check the protective device feeding the shed at the main board (and the shed sub-board) for a trip/off.
Devices on; nothing tripped.
2. If tripped, isolate shed circuits/appliances and reset to localise; if not, trace the submain for supply.
Cause localised (a shed circuit, appliance, or the submain).

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    No power to shed

    → step 2
  2. 2
    decision

    Has the device feeding the shed tripped/off?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does isolating shed circuits let it reset and hold?

    Yes→ step 5No→ step 6
  4. 4
    result

    Not tripped — trace the submain and shed wiring for supply/faults.

  5. 5
    result

    The shed circuit/appliance that drops it is the fault — rectify.

  6. 6
    result

    Trips with all off — submain/feed or earth fault; have it repaired.

Common mistakes apprentices make

  • Repeatedly resetting a tripping device feeding the shed.
  • Forgetting the shed may have its own sub-board.
  • Overlooking moisture/rodent damage to the submain.
  • Working in a damp outbuilding without isolating.

When to stop & escalate

Submains, sub-boards, and outbuilding wiring are licensed electrical work. A submain or earth fault must be found and repaired before re-energising.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults