Outdoor power point not working
An outdoor GPO is dead — often after rain — pointing at a tripped safety switch from moisture, a weatherproofing failure, or the outlet/run.
Safety first
Water and outdoor electricity are a shock risk. Isolate, prove dead, and never bypass the safety switch. Outdoor equipment must be weatherproof and suitable for the location.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
- 1
Safety switch tripped from moisture ingress
Most likelyWater in the outlet or its run has tripped the safety switch (common after rain).
- 2
Failed weatherproofing / water in the outlet
#2A perished seal or cracked cover lets water in, causing leakage/corrosion.
- 3
Outlet or run faulty
#3The GPO or the cabling to it has a fault (corrosion, damage).
- 4
Switched off / supply lost upstream
Least likelyAn indoor switch/circuit feeding it is off or tripped.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Check whether the safety switch has tripped and whether the outlet is wet / weatherproofing has failed.
Safety switch on; outlet dry and sealed.
Dry and not tripped — trace supply/the outlet.
Tripped from moisture / failed seal — dry out, reseal, and rectify.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Outdoor GPO dead
→ step 2 - 2decision
Is the outlet dry/sealed and the safety switch not tripped?
Yes→ step 3No→ step 4 - 3decision
Is the outlet/run sound and supply present?
Yes→ step 5No→ step 6 - 4result
Tripped from moisture / failed seal — dry, reseal, rectify.
- 5result
Dry outlet but dead with supply — replace the outlet.
- 6result
Water-damaged outlet/run or no supply — rectify.
Common mistakes apprentices make
- Bypassing the safety switch to restore outdoor power.
- Not addressing the weatherproofing that let water in.
- Reusing a corroded/water-damaged outlet.
- Overlooking an indoor switch/circuit feeding it.
When to stop & escalate
Outdoor electrical work is licensed and must use weatherproof, location-suitable equipment. Never run outdoor circuits on defeated earth-leakage protection.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
Safety switch (RCD) keeps tripping at the switchboard
The safety switch trips repeatedly — instantly on reset, randomly, or when certain appliances run. It's detecting earth leakage somewhere; the job is to find where.
RCD trips only in wet weather or after wash-down
The RCD holds fine when dry but trips after rain, washdown, or in damp conditions — pointing to moisture creating an earth-leakage path somewhere outdoors or in wet areas.
Outdoor / garden light not working
An outdoor or garden light is out — could be the lamp, a sensor/timer, weatherproofing/water ingress, or the supply.