QualifiedMedium risk

Forward/reverse interlock locking out both directions

Neither direction will run — the interlock that stops both contactors closing together appears to be holding everything off, so no movement at all.

Safety first

Confirm what the interlock protects before touching it. The motor can start the moment the interlock clears, possibly in an unexpected direction.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    One direction's contactor stuck closed/aux not resetting

    Most likely

    If one contactor (or its aux interlock contact) is stuck, the interlock keeps the other locked out permanently.

  2. 2

    Mis-wired interlock holding both off

    #2

    An interlock wired wrongly can hold both directions out instead of just preventing overlap.

  3. 3

    Common control fault upstream

    #3

    A shared fault (control supply, e-stop, overload) stops either direction regardless of the interlock.

  4. 4

    Mechanical interlock jammed

    Least likely

    A mechanical interlock bar between the contactors has jammed, blocking both.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Check both direction contactors are fully released at rest (none stuck, aux contacts reset).

Expected reading

Both contactors open and their aux interlock contacts reset.

If it passes

Both released — check the interlock wiring and common control.

If it fails

One stuck contactor/aux is holding the interlock — free/replace it.

Mark this test
View all expected readings at once
1. Check both direction contactors are fully released at rest (none stuck, aux contacts reset).
Both contactors open and their aux interlock contacts reset.
2. Confirm the common control path (supply, e-stop, overload) is healthy for both directions.
Control supply and permissives healthy.
3. Isolate and check the interlock wiring/mechanism against the drawings for a mis-wire or jam.
Interlock wired/working to prevent overlap only — not block both.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Neither direction runs

    → step 2
  2. 2
    decision

    Are both contactors fully released with aux contacts reset?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the common control path (supply/e-stop/overload) healthy?

    Yes→ step 5No→ step 6
  4. 4
    result

    One stuck contactor/aux holding the interlock — free or replace it.

  5. 5
    result

    Check interlock wiring/mechanism vs drawings for mis-wire or jam.

  6. 6
    result

    Shared control fault — fix that first.

Common mistakes apprentices make

  • Assuming a control fault when one contactor is simply stuck closed.
  • Removing the interlock to get running and risking simultaneous closure.
  • Not checking the common control path that affects both directions.
  • Reworking interlock wiring without the drawings.

When to stop & escalate

Never disable the interlock to restore operation — it prevents a dangerous fault. If the interlock logic is unclear, confirm against the drawings before any change.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.