QualifiedHigh risk

Contactor contacts welded closed — load won't switch off

The contactor won't drop out when the coil is de-energised. The load stays powered even with the control circuit off, because the main contacts have welded together.

Safety first

Welded contacts mean the load cannot be switched off by its normal control. Never rely on the coil to make it safe — isolate upstream and prove dead. Treat the load as live.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    High inrush or fault current welded the contacts

    Most likely

    Switching a heavy inductive or motor load, or closing onto a fault, can draw enough current to fuse the contact faces together.

  2. 2

    Worn / pitted contacts arcing on each operation

    #2

    Aged contacts with heavy pitting concentrate current on small points, building heat until they weld.

  3. 3

    Undersized or wrong-rated contactor

    #3

    A contactor rated below the actual switching duty wears and welds far sooner than expected.

  4. 4

    Chattering that arced the contacts together

    Least likely

    Prolonged chatter from a weak coil supply arcs repeatedly and can weld the faces.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

De-energise the coil and check whether the load actually drops out (observe / measure downstream).

Expected reading

Load de-energises cleanly when the coil is released.

If it passes

Contacts are releasing — the fault is elsewhere, not a weld.

If it fails

Load stays live with the coil off — a weld is confirmed.

View all expected readings at once
1. De-energise the coil and check whether the load actually drops out (observe / measure downstream).
Load de-energises cleanly when the coil is released.
2. Isolate, lock off, prove dead, then inspect the main contacts for welding, pitting and burning.
Clean, separable contacts that open freely.
3. Check the contactor's rating and duty against the actual load, and look for what caused the over-current (fault, stalled motor, chatter).
Contactor correctly rated for the load and switching duty.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Contactor won't drop out

    → step 2
  2. 2
    decision

    Does the load stay live with the coil de-energised?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Are the contact faces welded/badly pitted?

    Yes→ step 5No→ step 6
  4. 4
    result

    Contacts release fine — look elsewhere (control logic, not a weld).

  5. 5
    result

    Welded contacts — replace, then find the over-current cause and correct rating.

  6. 6
    result

    Clean but stuck — suspect a mechanical jam in the contactor.

Common mistakes apprentices make

  • Assuming the control circuit failed when the contacts have actually welded.
  • Replacing the contactor without finding why it welded — it will happen again.
  • Relying on the coil/control to isolate a welded contactor for working on the load.
  • Fitting a like-for-like device when the duty really needs a higher rating.

When to stop & escalate

If the load can't be positively isolated by its normal means, treat it as a safety issue and isolate upstream before any work. Repeated welding points to a sizing or fault-current problem that should be designed out, not just re-fitted.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.