QualifiedHigh risk

Motor goes one way but won't go the other (e.g. down but not up)

A reversing drive works in one direction only. One command (say, down) runs fine; the other (up) does nothing, or just hums/trips. Common on hoists, doors, and conveyors.

Safety first

Reversing gear often drives hoists, doors, and lifts — anything that moves can crush. Confirm the load is mechanically secured and the area clear before testing direction commands.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Failed direction contactor (the 'up' one)

    Most likely

    Each direction usually has its own contactor. If the up contactor's coil or contacts have failed, that direction is dead while the other still works.

  2. 2

    Tripped/triggered direction limit or interlock

    #2

    An end-of-travel limit, slack-rope switch, or safety interlock for that direction is opening the circuit, so the command can't get through.

  3. 3

    Broken control wiring or button for one direction

    #3

    A faulty 'up' pushbutton, broken pendant wire, or open seal-in contact only affects that one direction's control path.

  4. 4

    Mechanical end-stop or jammed load in that direction

    #4

    The load is already against a physical end-stop or jammed, so it can't travel further that way even though the electrics are fine.

  5. 5

    Phase/contact issue causing a trip only one way

    Least likely

    A weak contact on one direction contactor can cause single-phasing that trips or stalls only when that contactor is used.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 4
1

Operate the failing direction and listen/look: does the direction contactor try to pull in at all?

Expected reading

The up contactor energises (clunk) when you press up.

If it passes

The contactor is being commanded — focus on the contactor contacts, motor connection, or a trip.

If it fails

The contactor isn't being told to come in — the fault is in that direction's control path (button, wiring, limit, interlock).

Mark this test
View all expected readings at once
1. Operate the failing direction and listen/look: does the direction contactor try to pull in at all?
The up contactor energises (clunk) when you press up.
2. If the contactor doesn't energise, trace the control path for that direction: check its limit switch, interlock, and pushbutton continuity.
Closed (made) limit/interlock contacts and a working button when that direction is selected.
3. If the contactor does energise, isolate/lock off and inspect its main contacts; compare to the known-good direction contactor.
Clean contacts that make on all poles, matching the good direction's contactor.
4. Confirm there isn't a mechanical end-stop already reached: check position vs travel limits.
The load has room to travel in the failing direction.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Runs one way, not the other

    → step 2
  2. 2
    decision

    Does the failing-direction contactor pull in when commanded?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Are the contactor's main contacts good and is there travel left?

    Yes→ step 5No→ step 6
  4. 4
    decision

    Is that direction's control path (limit/interlock/button) complete?

    Yes→ step 7No→ step 8
  5. 5
    result

    Check motor wiring and for single-phasing on that direction's path.

  6. 6
    result

    Burnt contacts or at end-of-travel. Replace contacts / confirm position.

  7. 7
    result

    Path complete but coil won't pull in — see contactor coil fault-finding.

  8. 8
    result

    Open limit, interlock, or button is blocking the command. Repair that path.

Common mistakes apprentices make

  • Assuming the motor is faulty when only one direction's contactor or limit has failed — the other direction proves the motor turns.
  • Forgetting the mechanical interlock between the two contactors and condemning a contactor that's actually being held off.
  • Not checking the end-of-travel limit for the failing direction.
  • Swapping the motor before proving the up command even reaches the contactor.

When to stop & escalate

On hoists, lifts, and doors, any safety interlock or end-of-travel limit found operating should be confirmed against the machine's safety design before being adjusted or bypassed. If the load is jammed mechanically, hand it to the mechanical team.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.