QualifiedHigh risk

Reversing starter trips when changing direction

The drive runs each direction on its own but trips protection when you change from forward to reverse (or vice versa), often if the changeover is too quick.

Safety first

Reversing a spinning motor (plugging) draws very high current and stresses the drivetrain. Ensure the load can take it and the area is clear before testing changeovers.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    No off-delay between directions (plugging)

    Most likely

    Switching straight from forward to reverse while the motor is still spinning causes a huge current surge that trips protection.

  2. 2

    Interlock timing too tight

    #2

    The changeover interlock isn't allowing the first contactor to fully drop before the second closes.

  3. 3

    Both contactors briefly closing

    #3

    A failed or mis-wired interlock lets both direction contactors close together momentarily, creating a phase-to-phase fault.

  4. 4

    High load inertia

    Least likely

    A high-inertia load takes longer to stop, so an immediate reverse plugs hard and trips.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Check whether the control allows the motor to stop (or an off-delay) before reversing.

Expected reading

A stop/off-delay between directions so the motor isn't reversed while spinning.

If it passes

There's a delay — check the interlock timing and wiring.

If it fails

No delay — direct plugging is causing the trip; add a delay or stop step.

View all expected readings at once
1. Check whether the control allows the motor to stop (or an off-delay) before reversing.
A stop/off-delay between directions so the motor isn't reversed while spinning.
2. Verify the changeover interlock lets the first contactor fully drop before the second closes.
Clean, sequential changeover with no overlap.
3. Isolate and confirm the electrical/mechanical interlock prevents both contactors closing together.
Interlock positively prevents simultaneous closure.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Trips on direction change

    → step 2
  2. 2
    decision

    Is there a stop/off-delay before reversing?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does the interlock let one contactor fully drop before the other closes?

    Yes→ step 5No→ step 6
  4. 4
    result

    Direct plugging — add a stop step / off-delay.

  5. 5
    result

    Review load inertia / changeover method.

  6. 6
    result

    Overlapping changeover — correct the interlock (never bypass).

Common mistakes apprentices make

  • Allowing direct forward-to-reverse switching while the motor is still spinning.
  • Defeating or weakening the changeover interlock to 'fix' nuisance trips.
  • Ignoring high load inertia that needs a stop before reverse.
  • Not confirming both contactors can't close together.

When to stop & escalate

The forward/reverse interlock prevents a dangerous phase-to-phase fault — never bypass it. If the application genuinely needs rapid reversing, the changeover method should be designed for it (e.g. controlled stop), not forced.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.