ApprenticeMedium risk

Outdoor / garden light not working

An outdoor or garden light is out — could be the lamp, a sensor/timer, weatherproofing/water ingress, or the supply.

Safety first

Isolate and prove dead before working. Outdoor fittings must be weatherproof; check seals when working on them.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Failed lamp / fitting

    Most likely

    The globe/LED or integrated fitting has failed.

  2. 2

    Sensor / timer / daylight setting

    #2

    A PIR/timer/daylight control isn't activating the light (or is set to night-only).

  3. 3

    Water ingress / failed weatherproofing

    #3

    Moisture in the fitting causes failure or tripping.

  4. 4

    Supply / switch fault

    Least likely

    A switch, transformer (for low-voltage garden lighting), or circuit fault.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 2
1

Try a known-good lamp and check any sensor/timer/daylight settings.

Expected reading

Works with a good lamp and correct settings.

If it passes

It was the lamp/settings — done.

If it fails

Still out — check weatherproofing/water and supply.

Mark this test
View all expected readings at once
1. Try a known-good lamp and check any sensor/timer/daylight settings.
Works with a good lamp and correct settings.
2. Isolate and inspect for water ingress; confirm supply (and any transformer for low-voltage lighting).
Dry fitting and supply present.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Outdoor light out

    → step 2
  2. 2
    decision

    Does a known-good lamp + correct settings work?

    Yes→ step 3No→ step 4
  3. 3
    result

    It was the lamp/settings — done.

  4. 4
    decision

    Is the fitting dry and supply (transformer) present?

    Yes→ step 5No→ step 6
  5. 5
    result

    Dry fitting but dead with supply — replace the fitting.

  6. 6
    result

    Water ingress or no supply/transformer fault — rectify.

Common mistakes apprentices make

  • Not checking a sensor/daylight setting that blocks daytime testing.
  • Ignoring water ingress in the fitting.
  • Overlooking a failed low-voltage transformer for garden lighting.
  • Working live on an outdoor fitting.

When to stop & escalate

Outdoor lighting work is licensed electrical with weatherproof, suitable equipment. Low-voltage garden lighting transformers/wiring should also be checked by a licensed person.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults