Motion-sensor light not working correctly
A sensor (PIR) light won't come on, stays on permanently, or triggers at the wrong times — common on eaves, garages, and entries.
Safety first
Isolate before adjusting or replacing the fitting. Outdoor fittings should be weatherproof — check seals when working on them.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
- 1
Mode / settings wrong (test, time, lux)
Most likelyMany PIR lights have test/auto modes, on-time, and daylight (lux) settings that, set wrong, cause odd behaviour.
- 2
Sensor aimed/located poorly
#2Wrong aim or range means it misses movement or triggers on traffic/animals.
- 3
Daylight cut-off active
#3Set to night-only, it won't activate in daylight (working as intended) — or the lux setting is wrong.
- 4
Faulty sensor or lamp
Least likelyThe PIR head or the lamp has failed.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Check the mode and settings (test mode, on-time, lux/daylight) match what you expect.
Settings consistent with the desired behaviour.
Settings fine — check aim/range and the lamp/sensor.
Wrong mode/settings — set them correctly and re-test.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Sensor light faulty
→ step 2 - 2decision
Are mode and settings (time/lux) correct?
Yes→ step 3No→ step 4 - 3decision
Is the aim/coverage right (and tested in suitable light)?
Yes→ step 5No→ step 6 - 4result
Set the correct mode/settings and re-test.
- 5decision
Do the lamp and sensor head test healthy?
Yes→ step 7No→ step 8 - 6result
Re-aim/relocate the sensor.
- 7result
Re-verify settings/aim.
- 8result
Faulty lamp/sensor — replace.
Common mistakes apprentices make
- Testing in daylight when the lux setting blocks daytime operation.
- Leaving it in test mode (short on-time) and thinking it's faulty.
- Poor aim so it misses the intended approach.
- Replacing the fitting before checking the settings.
When to stop & escalate
Replacement and any wiring is licensed electrical work. Persistent false triggers from a fundamentally poor location may need the fitting repositioned.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
Outdoor / garden light not working
An outdoor or garden light is out — could be the lamp, a sensor/timer, weatherproofing/water ingress, or the supply.
A single light not working
One light fitting is dead while the rest of the lights on the circuit work fine — points at the lamp, the fitting, or the switch for that point rather than the whole circuit.
Outdoor power point not working
An outdoor GPO is dead — often after rain — pointing at a tripped safety switch from moisture, a weatherproofing failure, or the outlet/run.