ApprenticeMedium risk

Double power point — one side works, one doesn't

On a double GPO, one socket works and the other is dead — usually an internal fault in the outlet or a loose link between the two sockets.

Safety first

Isolate and prove dead before opening the outlet — the working side proves the point is live.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Internal fault in the GPO

    Most likely

    The dead socket's internal contacts or link have failed within the outlet.

  2. 2

    Loose link between the two sockets

    #2

    The internal link/bridge feeding the second socket is loose or broken.

  3. 3

    Damaged socket contacts

    Least likely

    Worn or burnt contacts on one socket (e.g. from a poor plug fit/arcing).

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 2
1

Confirm only one socket of the double is dead (test both with a known-good appliance).

Expected reading

One socket works, the other is dead.

If it passes

Single-socket fault — isolate and inspect the outlet.

If it fails

If both are dead, treat it as a dead GPO (trace the supply).

View all expected readings at once
1. Confirm only one socket of the double is dead (test both with a known-good appliance).
One socket works, the other is dead.
2. Isolate, prove dead, and inspect the outlet's internal link and contacts.
Sound internal link and clean contacts.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    One socket of double dead

    → step 2
  2. 2
    decision

    Is only one socket of the double dead?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Are the internal link and contacts sound?

    Yes→ step 5No→ step 6
  4. 4
    result

    Both dead — treat as a dead GPO; trace the supply.

  5. 5
    result

    Looks fine but a socket is dead — replace the outlet.

  6. 6
    result

    Loose link / burnt contacts — replace the outlet.

Common mistakes apprentices make

  • Assuming the whole circuit when only one socket of a double is dead.
  • Reusing a GPO with burnt/arced contacts.
  • Not isolating because 'the other side still works'.
  • Overlooking a loose internal link.

When to stop & escalate

Replacing a GPO is licensed electrical work. Burnt contacts suggest a poor plug fit or overload worth noting.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults