Double power point — one side works, one doesn't
On a double GPO, one socket works and the other is dead — usually an internal fault in the outlet or a loose link between the two sockets.
Safety first
Isolate and prove dead before opening the outlet — the working side proves the point is live.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Internal fault in the GPO
Most likelyThe dead socket's internal contacts or link have failed within the outlet.
- 2
Loose link between the two sockets
#2The internal link/bridge feeding the second socket is loose or broken.
- 3
Damaged socket contacts
Least likelyWorn or burnt contacts on one socket (e.g. from a poor plug fit/arcing).
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeConfirm only one socket of the double is dead (test both with a known-good appliance).
One socket works, the other is dead.
Single-socket fault — isolate and inspect the outlet.
If both are dead, treat it as a dead GPO (trace the supply).
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
One socket of double dead
→ step 2 - 2decision
Is only one socket of the double dead?
Yes→ step 3No→ step 4 - 3decision
Are the internal link and contacts sound?
Yes→ step 5No→ step 6 - 4result
Both dead — treat as a dead GPO; trace the supply.
- 5result
Looks fine but a socket is dead — replace the outlet.
- 6result
Loose link / burnt contacts — replace the outlet.
Common mistakes apprentices make
- Assuming the whole circuit when only one socket of a double is dead.
- Reusing a GPO with burnt/arced contacts.
- Not isolating because 'the other side still works'.
- Overlooking a loose internal link.
When to stop & escalate
Replacing a GPO is licensed electrical work. Burnt contacts suggest a poor plug fit or overload worth noting.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
Power point (GPO) completely dead
Nothing plugged into a power point works, while other outlets are fine. A classic trace-it-back fault on a single GPO or the run feeding it.
Power point burnt, melted, or smells hot
A GPO is discoloured, melted, or gives off a burning smell — a serious fire-risk fault from arcing/overheating at the outlet, usually from a poor plug fit or overload.
Half the power points in the house not working
A group of outlets across several rooms is dead together while lights and other GPOs work — points at one power circuit's protection or a shared upstream fault.