QualifiedHigh risk

Power point burnt, melted, or smells hot

A GPO is discoloured, melted, or gives off a burning smell — a serious fire-risk fault from arcing/overheating at the outlet, usually from a poor plug fit or overload.

Safety first

This is a fire risk — stop using the outlet immediately. Isolate the circuit, prove dead, and don't re-energise until it's repaired and the cause found. Burnt terminals can be brittle.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Loose terminal / poor connection arcing

    Most likely

    A loose conductor at the outlet arcs and overheats, melting and scorching the GPO — the most common cause.

  2. 2

    Sustained overload from a high-draw appliance

    #2

    A heater, dryer, or similar drawing near the limit (especially via a worn socket) overheats the outlet.

  3. 3

    Worn socket / poor plug fit

    #3

    A loose-fitting plug arcs at the contacts, building heat.

  4. 4

    Daisy-chained loads / double adaptors

    Least likely

    Piggybacked high loads overload the outlet.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Stop using it, isolate the circuit, prove dead, and remove the damaged outlet to inspect.

Expected reading

A clear view of the damaged terminals/contacts.

If it passes

Inspect for the cause (loose terminal, burnt contacts).

If it fails

If the damage extends to the cable, more rectification is needed.

View all expected readings at once
1. Stop using it, isolate the circuit, prove dead, and remove the damaged outlet to inspect.
A clear view of the damaged terminals/contacts.
2. Identify the cause: loose terminal arcing, overloaded outlet, or worn socket/poor plug fit.
A definite cause found.
3. Replace the outlet, ensure conductors are sound, and confirm the load/plug-fit issue is addressed.
New outlet, sound terminations, appropriate loading.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    GPO burnt/melted

    → step 2
  2. 2
    decision

    After isolating, are the conductors sound (not heat-damaged)?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the cause clear (loose terminal / overload / poor plug fit)?

    Yes→ step 5No→ step 6
  4. 4
    result

    Cut back to sound copper and remake before fitting a new outlet.

  5. 5
    result

    Rectify cause + replace outlet; advise on loading/plug fit.

  6. 6
    result

    Cause unclear / recurring — review the loading and circuit.

Common mistakes apprentices make

  • Just swapping the GPO without finding why it burnt.
  • Reconnecting heat-damaged conductors instead of cutting back to sound copper.
  • Ignoring the appliance/loading that caused the overload.
  • Continuing to use a scorched outlet.

When to stop & escalate

This is licensed electrical work and a fire-safety priority — repair promptly, find the cause, and rectify any damaged cabling. Recurring overheating points to a loading or circuit issue to assess.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults