Power point (GPO) completely dead
Nothing plugged into a power point works, while other outlets are fine. A classic trace-it-back fault on a single GPO or the run feeding it.
Safety first
A dead outlet can still have live terminals or become live. Isolate and prove dead before opening it; prove your tester before and after. Watch for a lost neutral making a 'dead' point hazardous.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
- 1
Circuit protective device tripped/off
Most likelyThe breaker/RCBO for that circuit has tripped or is switched off.
- 2
Loose connection upstream on the run
#2A loose active/neutral at an upstream GPO breaks supply to everything beyond it (looped points).
- 3
Faulty outlet
#3The GPO itself has an internal fault or a loose terminal.
- 4
Switched GPO turned off
Least likelyThe outlet's own switch (or a wall switch controlling it) is off.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Check the GPO's own switch and the circuit's protective device at the board.
Outlet switched on; protective device on.
Both on — trace the run toward the dead outlet.
Switched off / tripped — restore (find why if it tripped).
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
GPO completely dead
→ step 2 - 2decision
Is the outlet switched on and the circuit device on?
Yes→ step 3No→ step 4 - 3decision
Tracing the run, does supply reach the outlet?
Yes→ step 5No→ step 6 - 4result
Restore the switch/device (find why it tripped).
- 5result
Supply reaches it — the outlet is faulty; replace it.
- 6result
Supply lost upstream — repair the loose connection at that point.
Common mistakes apprentices make
- Not proving the tester before and after (false 'dead' readings).
- Replacing the outlet before finding where supply is actually lost.
- Forgetting the outlet or a wall switch controls it.
- Missing a lost neutral that makes a dead point dangerous.
When to stop & escalate
Tracing and repairing fixed wiring is licensed electrical work. If the protective device re-trips when restored, find the fault before re-energising.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
Half the power points in the house not working
A group of outlets across several rooms is dead together while lights and other GPOs work — points at one power circuit's protection or a shared upstream fault.
Safety switch (RCD) keeps tripping at the switchboard
The safety switch trips repeatedly — instantly on reset, randomly, or when certain appliances run. It's detecting earth leakage somewhere; the job is to find where.
No supply at a socket-outlet or point
A socket-outlet or point is dead — nothing plugged in works — while other points may be fine. A bread-and-butter 'trace it back' fault.