ApprenticeMedium risk

Half the power points in the house not working

A group of outlets across several rooms is dead together while lights and other GPOs work — points at one power circuit's protection or a shared upstream fault.

Safety first

Don't repeatedly reset a tripping device. Isolate and prove dead. A lost neutral on a power circuit can put odd voltages on equipment — treat as hazardous.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Power circuit breaker/RCBO tripped

    Most likely

    One power circuit's protective device has tripped, killing all its outlets at once.

  2. 2

    Faulty appliance/outlet tripping the circuit

    #2

    A single faulty appliance or outlet on the circuit trips the protection.

  3. 3

    Loose connection at a shared point

    #3

    A loose active/neutral early in the run drops everything downstream.

  4. 4

    Lost neutral on the circuit

    Least likely

    A neutral fault can disable a group of outlets and cause strange behaviour.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Check the switchboard for a tripped power-circuit breaker/RCBO.

Expected reading

Nothing tripped on the power circuits.

If it passes

Not tripped — trace the shared run for a loose/neutral fault.

If it fails

Tripped — find what trips it before resetting.

Mark this test
View all expected readings at once
1. Check the switchboard for a tripped power-circuit breaker/RCBO.
Nothing tripped on the power circuits.
2. If tripped, unplug appliances on that circuit and reset; reintroduce them to find the culprit.
Circuit holds with appliances unplugged.
3. If not tripped, trace the shared connection/neutral feeding the dead outlets.
Sound active and neutral feeding the group.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Half the GPOs dead

    → step 2
  2. 2
    decision

    Has a power-circuit device tripped?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does unplugging appliances let it reset and hold?

    Yes→ step 5No→ step 6
  4. 4
    result

    Not tripped — trace the shared connection/neutral.

  5. 5
    result

    The appliance that re-trips it is faulty — remove/repair.

  6. 6
    result

    Trips with all unplugged — fault in the fixed wiring.

Common mistakes apprentices make

  • Resetting a tripping circuit repeatedly instead of finding the cause.
  • Not isolating appliances to separate an appliance fault from wiring.
  • Overlooking a loose neutral as the cause of a dead group.
  • Assuming a main fault when it's one circuit.

When to stop & escalate

Fixed-wiring and neutral faults are licensed electrical work and must be repaired before re-energising. A repeatedly tripping circuit indicates a real fault to find, not a device to upsize.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults