ApprenticeMedium risk

No supply at a socket-outlet or point

A socket-outlet or point is dead — nothing plugged in works — while other points may be fine. A bread-and-butter 'trace it back' fault.

Safety first

A 'dead' outlet can become live, or have live terminals nearby. Prove dead before working, and prove your tester before and after. Beware a lost neutral making a dead-looking point dangerous.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Tripped protective device for that circuit

    Most likely

    The breaker/RCD for the circuit has tripped or is off, killing the point.

  2. 2

    Open connection upstream (loose terminal)

    #2

    A loose or broken connection at an upstream point breaks supply to everything beyond it.

  3. 3

    Faulty outlet itself

    #3

    The socket/point has an internal fault or a loose terminal.

  4. 4

    Switch/control upstream off

    Least likely

    A switch, isolator, or control upstream is off, removing supply.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Check the circuit's protective device is on and hasn't tripped; verify supply at the board for that circuit.

Expected reading

Protective device on and supply present at the board.

If it passes

Supply leaves the board — trace toward the dead point.

If it fails

Tripped/off device — restore (and find why if it tripped).

Mark this test
View all expected readings at once
1. Check the circuit's protective device is on and hasn't tripped; verify supply at the board for that circuit.
Protective device on and supply present at the board.
2. Work along the circuit testing for supply at points/junctions to find where it's lost.
Supply present up to a point, then absent beyond it.
3. At the fault location, isolate and inspect the connection/outlet (loose terminal, break, internal fault).
A found loose/broken connection or a faulty outlet.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    No supply at point

    → step 2
  2. 2
    decision

    Is the protective device on and supply present at the board?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Tracing along, does supply reach the outlet?

    Yes→ step 5No→ step 6
  4. 4
    result

    Restore the tripped/off device (find why if it tripped).

  5. 5
    result

    Supply reaches it — the outlet itself is faulty; repair/replace.

  6. 6
    result

    Supply lost upstream — repair the open connection at that point.

Common mistakes apprentices make

  • Not proving the tester before and after (false 'dead' readings).
  • Replacing the outlet before tracing where supply is actually lost.
  • Forgetting an upstream switch/isolator that's off.
  • Missing a lost neutral that makes a 'dead' point hazardous.

When to stop & escalate

If a protective device trips again when restored, find the fault before re-energising. Tracing within fixed wiring should be done by a competent person following safe isolation.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.