AdvancedHigh risk

Solar inverter showing an isolation / earth fault (often after rain)

The inverter refuses to start (or shuts down) on an isolation, ISO, ground-fault or Riso error — classically first thing on a dewy morning or after rain, sometimes clearing as the day dries out. Something on the DC side is leaking to earth.

Safety first

PV strings are live in daylight and this fault means DC is finding a path to earth somewhere. No live DC work: never open connectors or isolators under load, and treat frames, rails and roof metal as suspect until the leak is found. In Australia the PV DC side is accredited-solar territory — this guide is the diagnostic logic, not a licence.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Water in a rooftop DC isolator

    Most likely

    The classic Australian failure — rooftop isolators fill with water, track to earth, and throw ISO faults that ease off as they dry. Many older models were the subject of recalls; treat any weathered one as suspect.

  2. 2

    Damaged string cable insulation

    #2

    Cable chafed on roof iron, tile edges or tray, cooked by heat, or chewed by vermin leaks to earth — worst when wet, which is why the fault loves mornings.

  3. 3

    Water in PV plug connectors or a junction

    #3

    Badly mated or non-matching plug pairs and unsealed junctions wick in moisture and track to the frame or roof.

  4. 4

    A damaged panel leaking through its frame

    #4

    Cracked backsheet or glass, or moisture inside a delaminating module, gives a leak path from the cells to the earthed frame.

  5. 5

    Inverter measurement circuit at fault

    Least likely

    Rare, but the Riso measurement itself can fail. Only conclude this after the array genuinely tests clean.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 4
1

Establish the pattern: does the fault appear on damp mornings and clear as the day warms up? Check the inverter log for times and (where shown) the measured isolation resistance.

Expected reading

Moisture-linked timing — faults at dawn/after rain that clear when dry — and a logged Riso value that dips below the inverter's threshold.

If it passes

Moisture-dependent = almost certainly isolator, connector or damaged cable getting wet. Physical inspection will probably find it.

If it fails

A hard fault in all weather is a solid leak — damaged cable or panel — and will show clearly on IR testing.

Mark this test
View all expected readings at once
1. Establish the pattern: does the fault appear on damp mornings and clear as the day warms up? Check the inverter log for times and (where shown) the measured isolation resistance.
Moisture-linked timing — faults at dawn/after rain that clear when dry — and a logged Riso value that dips below the inverter's threshold.
2. Shut the system down per its labelled procedure. Inspect the obvious water traps first: rooftop/wall DC isolators (open the lids), PV connectors, and any junction boxes — look for water, tracking marks, greening or heat damage.
Dry, clean isolators and properly mated, matching connector pairs.
3. Accredited/competent persons, system isolated per procedure: insulation-resistance test each string's conductors to earth (both polarities), following the inverter/system manual's method and test voltage.
High insulation resistance on every string — comfortably above the inverter's trip threshold (thresholds vary by unit; ballpark expectations are around the megohm mark or better dry — the manual states the number that matters).
4. Corner the leak: with the low string split at connectors, IR test each half, then quarters, until one panel, lead or the isolator is left holding the low reading.
Each split cleanly separates a good section from the low one, converging on a single component.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Inverter ISO / earth-fault error

    → step 2
  2. 2
    decision

    Does the fault come with damp (mornings/rain) and clear when dry?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Visible water/tracking in a DC isolator, connector or junction?

    Yes→ step 5No→ step 4
  4. 4
    decision

    Does IR testing show one string low to earth?

    Yes→ step 6No→ step 7
  5. 5
    result

    Replace the wet component properly and seal the water entry — drying it isn't a repair.

  6. 6
    result

    Halve-and-test along that string to corner the leak, then replace the section/component.

  7. 7
    result

    Array tests clean in all conditions → suspect the inverter's measurement — manufacturer support.

Common mistakes apprentices make

  • Restarting the inverter repeatedly until the fault 'clears' with the sun and calling it fixed — the leak is still there, waiting for rain.
  • Opening DC connectors or isolators under load — DC arcs and doesn't forgive.
  • Drying out a wet isolator and closing the lid instead of replacing it and fixing the water entry.
  • Blaming the inverter's measurement before actually IR-testing the strings.

When to stop & escalate

All of the on-roof DC diagnosis and repair belongs with accredited solar people — bring one in rather than improvising. Panel-level leakage is a warranty conversation with the datasheet and your IR readings attached. If the array genuinely tests clean in all conditions and the unit still faults, it's a manufacturer job on the inverter.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults