QualifiedHigh risk

Solar inverter dead, blank, or showing a fault

The rooftop solar has stopped generating — the inverter display is blank, or it's alive but sitting on a fault code. The owner usually notices when the power bill jumps.

Safety first

PV strings are LIVE whenever there's daylight — the DC side doesn't switch off with the sun up, and DC arcs don't self-extinguish. Never open DC isolators under load or open string wiring live. In Australia, work on the PV (DC) side is for accredited/appropriately competent people; the AC side to the board is ordinary licensed work. Isolate in the sequence the shutdown procedure label gives.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    AC supply to the inverter lost

    Most likely

    The dedicated solar breaker/main switch at the board is off or tripped, or an upstream RCD has taken it out. An inverter with no grid reference shuts down (anti-islanding) — many models also go completely blank without AC.

  2. 2

    DC isolator failed or switched off

    #2

    Rooftop and wall DC isolators are a notorious weak point — water ingress, heat damage, or simply left off after roof work. No DC in, nothing to convert.

  3. 3

    Grid outage or voltage/frequency outside limits

    #3

    The inverter is healthy but disconnected itself because the grid is out or outside its programmed window — it reconnects by itself once conditions return.

  4. 4

    Inverter internal failure

    #4

    Electrolytics, relays and boards do die — especially in units mounted in full sun. Both supplies present with a dead display points here.

  5. 5

    A specific fault code doing its job

    Least likely

    Isolation faults, earth faults and arc-fault detections deliberately stop generation — the code on the display (or app) is the diagnosis, so read it before pulling anything apart.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 4
1

Read before you touch: note any display/LED state or app fault code, and photograph it. Then check the dedicated solar breaker and any RCD at the switchboard.

Expected reading

Either a meaningful fault code, or a tripped/off solar breaker staring at you.

If it passes

A fault code directs the rest of the job (isolation fault → its own guide). A tripped breaker: find out why before simply resetting.

If it fails

No code, breaker on — verify the AC supply actually reaches the inverter next.

Mark this test
View all expected readings at once
1. Read before you touch: note any display/LED state or app fault code, and photograph it. Then check the dedicated solar breaker and any RCD at the switchboard.
Either a meaningful fault code, or a tripped/off solar breaker staring at you.
2. If you're licensed and it's safe: verify AC at the inverter's AC isolator/terminals (typically ~230 V to neutral) with the solar breaker on.
Normal mains voltage at the inverter's AC connection.
3. DC side, without opening anything under load: confirm the DC isolator(s) are ON and inspect for heat/water damage. If competent to do so per the system's procedure, verify string voltage at the inverter's DC input.
Isolators on and healthy; string voltage present in daylight, in the ballpark the system was designed for (it varies with panel count — the system documentation states it).
4. If everything is present and it still won't run: perform the manufacturer's restart sequence (shutdown procedure in reverse), then watch its startup self-test and reconnect timer.
The inverter boots, self-tests, waits its mandated reconnect delay (commonly a minute or so), then starts exporting.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Solar inverter dead or on a fault

    → step 2
  2. 2
    decision

    Is there a fault code on the display or app?

    Yes→ step 3No→ step 4
  3. 3
    result

    The code IS the diagnosis — follow it (isolation fault has its own guide).

  4. 4
    decision

    Solar breaker on and AC present at the inverter?

    Yes→ step 5No→ step 6
  5. 5
    decision

    DC isolators on, healthy, and string voltage present in daylight?

    Yes→ step 7No→ step 8
  6. 6
    result

    AC supply fault — find why the breaker/RCD is out or trace the run to the inverter.

  7. 7
    result

    Both supplies present + dead unit = inverter failure. Manufacturer/installer job.

  8. 8
    result

    DC-side fault (isolator, connector, string) — accredited solar diagnosis, no live DC work.

Common mistakes apprentices make

  • Cycling isolators in random order under full sun — follow the labelled shutdown/startup sequence.
  • Resetting a tripped solar breaker or RCD without asking what tripped it.
  • Blaming the inverter without checking the humble AC breaker first — it's the most common 'fault'.
  • Ignoring the fault code and app history, which often names the problem outright.

When to stop & escalate

String/rooftop DC faults, isolation faults and anything requiring panels or DC wiring to be opened belong with an accredited solar electrician. Inverter internal failures are manufacturer-warranty jobs — don't open the unit. If it disconnected on grid limits repeatedly, see the grid-overvoltage guide.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults