QualifiedMedium risk

Reversing circuit runs the same direction both ways

Selecting forward or reverse both turn the motor the same way — the direction never actually changes, even though both contactors operate.

Safety first

Working on the reversing wiring means live-capable power terminals — isolate and prove dead. Confirm the driven equipment is safe to run in either direction during testing.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Reverse contactor not swapping two phases

    Most likely

    Reversing relies on the reverse contactor crossing two phases. If it's wired straight through, both directions are identical.

  2. 2

    Wiring error on the reverse contactor outputs

    #2

    The phase crossover was landed wrong during installation or a repair.

  3. 3

    Both directions driven by the same contactor

    Least likely

    A control fault energises the same (forward) contactor regardless of which button is pressed.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 2
1

Select reverse and confirm the reverse contactor (not the forward one) is the one energising.

Expected reading

The correct contactor energises for each direction.

If it passes

Right contactor operates — check its phase-crossover wiring.

If it fails

Same contactor for both — fix the control so each button drives its own contactor.

Mark this test
View all expected readings at once
1. Select reverse and confirm the reverse contactor (not the forward one) is the one energising.
The correct contactor energises for each direction.
2. Isolate and check the reverse contactor's output wiring crosses two phases relative to forward.
Two phases swapped on the reverse contactor's output.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Same direction both ways

    → step 2
  2. 2
    decision

    Does the correct (reverse) contactor energise on reverse?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does the reverse contactor cross two phases?

    Yes→ step 5No→ step 6
  4. 4
    result

    Same contactor for both — fix the control so each button drives its own.

  5. 5
    result

    Re-verify which contactor runs for each command.

  6. 6
    result

    No phase crossover — correct the reverse wiring.

Common mistakes apprentices make

  • Assuming the motor can't reverse when the wiring simply doesn't cross phases.
  • Not checking which contactor actually energises for each direction.
  • Landing the phase crossover wrong after a repair.

When to stop & escalate

If the reversing scheme is part of a larger control system and the wiring doesn't match the drawings, confirm the intended design before rewiring.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults