AdvancedHigh risk

RCBO tripping — telling overload from earth leakage

An RCBO (combined RCD + MCB) keeps tripping and you need to know whether it's tripping on overcurrent/overload or on earth leakage — the fix is very different for each.

Safety first

An RCBO can trip for two very different reasons — earth leakage (shock risk) or overcurrent (overload/short). Don't keep resetting; identify which, and treat both as real.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Earth-leakage fault (RCD side)

    Most likely

    Leakage to earth on the circuit trips the RCD function — same causes as any RCD trip.

  2. 2

    Overload (MCB side)

    #2

    Too much load current for the rating trips the overcurrent function, usually after running a while.

  3. 3

    Short circuit (MCB side)

    #3

    A short trips the overcurrent function instantly and hard.

  4. 4

    Neutral-earth fault

    Least likely

    A neutral-earth fault trips the RCD side, sometimes confusingly.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Note the trip behaviour: instant on energising (short), after running a while (overload), or seemingly random/at switch-on (leakage). Use any trip indicator the RCBO provides.

Expected reading

A pattern (and indicator) suggesting overcurrent vs leakage.

If it passes

Overcurrent pattern → treat as overload/short. Leakage pattern → treat as RCD trip.

If it fails

If unclear, separate the two by testing load current and insulation.

Mark this test
View all expected readings at once
1. Note the trip behaviour: instant on energising (short), after running a while (overload), or seemingly random/at switch-on (leakage). Use any trip indicator the RCBO provides.
A pattern (and indicator) suggesting overcurrent vs leakage.
2. For a suspected overcurrent trip, measure the circuit load current against the RCBO rating and check for a short.
Load within rating and no short.
3. For a suspected leakage trip, isolate and insulation-test the circuit to earth (and for neutral-earth faults).
Good insulation to earth and no neutral-earth fault.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    RCBO tripping

    → step 2
  2. 2
    decision

    Does the pattern/indicator point to overcurrent?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is load within rating with no short?

    Yes→ step 4No→ step 5
  4. 4
    decision

    Is insulation to earth good (no neutral-earth fault)?

    Yes→ step 6No→ step 7
  5. 5
    result

    Overload/short — address the load/wiring (MCB side).

  6. 6
    result

    Re-examine for cumulative leakage / appliances.

  7. 7
    result

    Earth/neutral-earth leakage — repair it (RCD side).

Common mistakes apprentices make

  • Treating every RCBO trip as 'earth leakage' (or vice versa).
  • Ignoring the RCBO's own trip indicator if it has one.
  • Resetting repeatedly into a short.
  • Not separating load-current testing from insulation testing.

When to stop & escalate

Confirmed overload may need load redistribution or a rating review; confirmed leakage needs a wiring/appliance repair. Both are real — never bypass an RCBO.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.