RCBO tripping — telling overload from earth leakage
An RCBO (combined RCD + MCB) keeps tripping and you need to know whether it's tripping on overcurrent/overload or on earth leakage — the fix is very different for each.
Safety first
An RCBO can trip for two very different reasons — earth leakage (shock risk) or overcurrent (overload/short). Don't keep resetting; identify which, and treat both as real.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
Premium fault tree
The full ranked causes, test sequence and flowchart for this fault are part of Sparkie Sidekick Pro.
Coming soon — no payment required during preview.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Full test sequence
The step-by-step test flow with expected readings for this fault is part of Sparkie Sidekick Pro.
Coming soon — no payment required during preview.
Fault-finding flowchart
The same logic as a decision tree.
- 1start
RCBO tripping
→ step 2 - 2decision
Does the pattern/indicator point to overcurrent?
Yes→ step 3No→ step 4 - 3decision
Is load within rating with no short?
Yes→ step 4No→ step 5 - 4decision
Is insulation to earth good (no neutral-earth fault)?
Yes→ step 6No→ step 7 - 5result
Overload/short — address the load/wiring (MCB side).
- 6result
Re-examine for cumulative leakage / appliances.
- 7result
Earth/neutral-earth leakage — repair it (RCD side).
Common mistakes apprentices make
- Treating every RCBO trip as 'earth leakage' (or vice versa).
- Ignoring the RCBO's own trip indicator if it has one.
- Resetting repeatedly into a short.
- Not separating load-current testing from insulation testing.
When to stop & escalate
Confirmed overload may need load redistribution or a rating review; confirmed leakage needs a wiring/appliance repair. Both are real — never bypass an RCBO.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
RCD / RCBO keeps tripping
An RCD or RCBO trips repeatedly — immediately on reset, randomly during the day, or only when certain equipment runs. The earth-leakage protection is doing its job; something is leaking.
Motor overload keeps tripping
The thermal/electronic overload trips repeatedly, either on start or after the motor has run for a while. Resetting only buys you a short run before it trips again.
RCD won't reset at all
The RCD won't stay reset — the toggle won't latch up, or it trips instantly every time, so the circuit can't be restored.
Learn the theory
How the gear and circuits behind this fault actually work.