ApprenticeMedium risk

Overload relay won't reset

After an overload trip, the reset won't take — the starter won't re-arm, or it resets and trips straight back. The control circuit stays broken at the overload's contact.

Safety first

An overload that won't reset is often still protecting against a real fault. Don't force it; resetting can restart machinery — confirm it's safe first.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Not enough cool-down time (thermal type)

    Most likely

    A thermal overload needs time to cool before it will reset after a trip.

  2. 2

    Underlying fault still present

    #2

    If the cause (jam, single-phasing, overcurrent) is still there, it resets then trips immediately.

  3. 3

    Reset set to manual/auto incorrectly

    #3

    The reset mode (hand/auto) is set wrong for the application, so it doesn't behave as expected.

  4. 4

    Mechanical fault in the reset mechanism

    Least likely

    A damaged reset button or trip mechanism won't latch back even with no fault.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Allow a thermal overload to cool, then attempt the reset.

Expected reading

It resets cleanly once cooled.

If it passes

It was just cool-down — done, but note why it tripped.

If it fails

Still won't reset or trips again — investigate further.

View all expected readings at once
1. Allow a thermal overload to cool, then attempt the reset.
It resets cleanly once cooled.
2. Reset and watch: does it hold, or trip again? If it trips, measure motor currents on the next attempt.
It holds with balanced currents within rating.
3. Check the reset mode setting (hand/auto) and the mechanical reset action with the circuit isolated.
Correct reset mode and a sound reset mechanism.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Overload won't reset

    → step 2
  2. 2
    decision

    Does it reset after cool-down?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does it hold with balanced, in-rating current?

    Yes→ step 5No→ step 6
  4. 4
    decision

    Is the reset mode correct and mechanism sound?

    Yes→ step 7No→ step 8
  5. 5
    result

    One-off trip — monitor; note the original cause.

  6. 6
    result

    Trips again — chase the real overload (jam/single-phasing/overcurrent).

  7. 7
    result

    Re-examine the load — something is still tripping it.

  8. 8
    result

    Correct the reset mode / replace a broken mechanism.

Common mistakes apprentices make

  • Hammering the reset before a thermal overload has cooled.
  • Resetting repeatedly into a real fault instead of finding it.
  • Not knowing whether the overload is set to hand or auto reset.
  • Condemning the overload when the load is genuinely overloaded.

When to stop & escalate

If it trips again on reset with high or unbalanced current, stop and find the load/supply fault before re-energising. A broken reset mechanism means replacing the overload.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.