Motor overload trips after running for a while
The motor starts and runs fine, then the thermal overload trips minutes or hours later. Reset it and it runs again before tripping once more — a heat/loading pattern, not a start fault.
Safety first
A motor that overloads in service can be genuinely overloaded or developing a fault — both can run hot. Don't just keep resetting it. Confirm isolation before working on terminals, and let a hot motor cool safely.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Mechanical load too high / increasing
Most likelyA binding bearing, tight belt, blocked impeller, or a process drawing more than design makes the motor pull above its rated current until the overload trips on accumulated heat.
- 2
High ambient or poor motor cooling
#2Blocked cooling fins, a failed fan, or a hot enclosure mean the motor and overload run hotter than expected and trip after a period of running.
- 3
Supply voltage low or unbalanced
#3Low voltage or phase imbalance makes the motor draw more current to do the same work, heating up over time and tripping the overload.
- 4
Overload set too low or wrong class
#4An overload dialled below the motor FLC, or the wrong trip class for the duty, trips on normal running current.
- 5
Developing winding fault
Least likelyA motor with a partial winding/insulation fault draws unbalanced or excess current that grows as it heats — a motor problem, not just loading.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeWith clamp meter on, run the motor and compare running current per phase against the nameplate FLC.
Balanced running current at or below nameplate FLC.
Current is within rating — suspect cooling, ambient, or an overload set too low.
Running current above FLC (or unbalanced) points to mechanical loading, low/unbalanced supply, or a winding fault.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Overload trips after running a while
→ step 2 - 2decision
Is running current at/below FLC and balanced?
Yes→ step 3No→ step 4 - 3decision
Is the overload set correctly (FLC, right class)?
Yes→ step 5No→ step 6 - 4decision
Does the driven load turn freely and cooling is clear?
Yes→ step 7No→ step 8 - 5result
Suspect cooling/ambient — check fan, fins, enclosure heat.
- 6result
Overload set too low / wrong class — correct the setting (not above FLC).
- 7result
Check supply voltage/balance and windings — address supply fault or remove motor for repair.
- 8result
Mechanical drag / blocked cooling overloading the motor — fix it.
Common mistakes apprentices make
- Repeatedly resetting the overload instead of finding why current is high.
- Winding the overload up to stop the trips — defeating the protection.
- Measuring only at start and missing that current climbs as the motor heats.
- Ignoring a failed cooling fan or blocked fins.
When to stop & escalate
Never increase the overload setting beyond the motor's FLC to stop tripping — that removes protection. Escalate a suspected winding fault for proper motor testing/repair, and a process overload for mechanical investigation.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
Motor overload keeps tripping
The thermal/electronic overload trips repeatedly, either on start or after the motor has run for a while. Resetting only buys you a short run before it trips again.
Motor running hot / overheating
The motor runs but gets excessively hot — too hot to touch, smell of hot insulation, or thermal protection cutting in after a while.
Three-phase equipment running hot from supply imbalance
Three-phase equipment (motors, heaters, large gear) runs hotter than expected or nuisance-trips, traced to a voltage/current imbalance between phases rather than the equipment itself.