AdvancedHigh risk

Motor with low insulation resistance to earth

An insulation resistance test on the motor reads low to earth — a sign the winding insulation is degraded, damp, or contaminated, risking trips and failure.

Safety first

Insulation testing applies a high test voltage — follow your test procedure, isolate, discharge, and ensure no one is in contact. A motor with low insulation can cause earth-leakage trips and shock risk.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Moisture / condensation in the windings

    Most likely

    Damp from standing idle, washdown, or a humid environment lowers insulation resistance, often recoverable by drying.

  2. 2

    Contamination (dust, oil, conductive debris)

    #2

    Build-up on the windings provides leakage paths to earth.

  3. 3

    Aged / heat-damaged insulation

    #3

    Years of heat cycling break down the insulation permanently.

  4. 4

    Physical damage to winding insulation

    Least likely

    A nick, abrasion, or burnt spot creates a direct low-resistance path to the frame.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Isolate, disconnect the motor, and carry out an insulation resistance test winding-to-earth per your procedure.

Expected reading

Insulation resistance well above the minimum your procedure allows.

If it passes

Insulation is adequate — the low reading may have been cabling; re-check.

If it fails

Low reading confirmed — determine whether it's moisture, contamination, or damage.

Mark this test
View all expected readings at once
1. Isolate, disconnect the motor, and carry out an insulation resistance test winding-to-earth per your procedure.
Insulation resistance well above the minimum your procedure allows.
2. Inspect for moisture/condensation and contamination; if damp, dry the motor per the recommended method and re-test.
Reading recovers after drying/cleaning if moisture/contamination was the cause.
3. If it doesn't recover, assess for aged or physically damaged insulation (visual, history, repeat tests).
A clear picture of whether the winding is serviceable.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Low insulation to earth

    → step 2
  2. 2
    decision

    With the motor disconnected, is IR still low?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does it recover after drying/cleaning?

    Yes→ step 5No→ step 6
  4. 4
    result

    Motor is fine — the low reading was in the cabling. Re-check that.

  5. 5
    result

    Moisture/contamination — restored; fix why it got in.

  6. 6
    result

    Aged/damaged winding — plan repair or replacement.

Common mistakes apprentices make

  • Testing with the motor still connected and blaming the motor for cable leakage.
  • Writing off a motor that just needs drying out.
  • Not addressing why moisture or contamination is getting in.
  • Ignoring a steadily falling reading over time until it fails.

When to stop & escalate

A winding that won't recover after drying needs a motor repair/rewind assessment. Recurrent moisture/contamination points to an environmental or sealing problem to fix at source.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.