QualifiedMedium risk

Jog / inch function not working

The jog (inch) control doesn't move the motor in short bursts — pressing jog does nothing, or it latches and runs continuously instead of jogging.

Safety first

Jog is often used during setup with guards open — extra caution. The motor moves on each press; keep hands and tools clear of the drivetrain.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Jog bypasses the seal-in — wiring fault

    Most likely

    Jog should energise the contactor without the seal-in latch. A wiring fault either blocks it or lets it latch and run on.

  2. 2

    Jog control/relay faulty

    #2

    A dedicated jog relay or its contacts have failed, so the jog path doesn't work.

  3. 3

    Jog button faulty

    #3

    The momentary jog button isn't making (does nothing) or is sticking (runs on).

  4. 4

    Interlock with run mode blocking jog

    Least likely

    A mode interlock between run and jog is mis-set, blocking jog.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Press jog and observe: nothing at all, or does it latch and run continuously?

Expected reading

Short burst of movement that stops when released.

If it passes

Jogging correctly — issue may be elsewhere.

If it fails

Nothing → check button/control path. Runs on → seal-in isn't being bypassed.

Mark this test
View all expected readings at once
1. Press jog and observe: nothing at all, or does it latch and run continuously?
Short burst of movement that stops when released.
2. Trace the jog path: jog button, jog relay/contacts, and how it bypasses the seal-in.
Jog energises the contactor without engaging the seal-in.
3. Check any run/jog mode selector or interlock is in the right state for jogging.
Mode set to allow jog.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Jog not working

    → step 2
  2. 2
    decision

    When you press jog, does it do nothing or run on continuously?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the jog path (button/relay/seal-in bypass) sound?

    Yes→ step 5No→ step 6
  4. 4
    result

    Jogs correctly — look elsewhere.

  5. 5
    decision

    Is the run/jog mode interlock set to allow jog?

    Yes→ step 7No→ step 8
  6. 6
    result

    Fault in jog button/relay or seal-in bypass — repair it.

  7. 7
    result

    Re-check the jog wiring.

  8. 8
    result

    Mode/interlock blocking jog — set correctly.

Common mistakes apprentices make

  • Not understanding that jog should bypass the seal-in (so it doesn't latch).
  • Missing a sticking jog button that makes it run on.
  • Overlooking a run/jog mode interlock.
  • Jogging near the drivetrain without keeping clear.

When to stop & escalate

Because jog is often used with guards open, treat any unexpected latching (run-on) as a priority safety fix. Confirm the jog logic against the drawings if unclear.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults