Power point reads voltage but the appliance won't run
You measure roughly normal voltage at the GPO, but plug in an appliance and nothing happens. The point isn't 'dead' on the meter, yet it won't drive a load.
Safety first
A point that reads voltage but can't supply current may have a broken neutral or a high-resistance joint that's live and dangerous. Treat it as live, and isolate before opening the accessory.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Open or high-resistance neutral
Most likelyWith an open neutral, a high-impedance meter still reads near-full voltage active-to-neutral through the appliance/parallel paths, but no real return path exists so no current flows and the appliance stays dead.
- 2
Phantom voltage on a disconnected active
#2Capacitive coupling from adjacent live cables induces a voltage a sensitive meter reads, even though the conductor isn't actually connected to a source that can deliver current.
- 3
High-resistance active connection
#3A loose or corroded active joint holds voltage with no load but collapses the instant the appliance draws current, so nothing runs.
- 4
Faulty appliance or its lead
Least likelyThe point may be fine — a tripped appliance thermal cutout, blown appliance fuse, or broken flex means the appliance won't run regardless.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeRe-measure with a loading-type tester (low-impedance) rather than only a high-impedance multimeter.
A loading tester confirms whether the voltage is a real, load-capable supply or a phantom.
Voltage holds under the tester's load — the supply is real, so look at the appliance/lead or a connection that sags under heavier load.
Voltage collapses under the tester — it was phantom or a high-resistance/open conductor, not a usable supply.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
GPO reads voltage but appliance won't run
→ step 2 - 2decision
Does voltage hold under a loading tester?
Yes→ step 3No→ step 4 - 3decision
Is neutral-to-earth close to zero?
Yes→ step 5No→ step 6 - 4result
Phantom or high-resistance/open conductor — trace the broken active/neutral.
- 5result
Supply is real — the appliance or its lead is faulty. Prove with a known-good load.
- 6result
Lost / high-resistance neutral upstream — trace and repair the neutral path.
Common mistakes apprentices make
- Trusting a high-impedance multimeter reading and declaring the point 'good'.
- Not checking neutral-to-earth, missing a lost neutral.
- Blaming the appliance before proving the point can actually supply current.
- Forgetting that a phantom voltage can't drive a load — the reading is misleading.
When to stop & escalate
A lost neutral can make exposed metalwork live elsewhere on the installation — if you suspect one, stop and investigate the shared neutral path before energising anything. Escalate if the fault is upstream of the point in an inaccessible part of the installation.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
Lost or high-resistance neutral
Strange symptoms across a circuit or installation — voltages going high and low on different loads, flickering, equipment damage — pointing to a lost or high-resistance neutral.
Power point (GPO) completely dead
Nothing plugged into a power point works, while other outlets are fine. A classic trace-it-back fault on a single GPO or the run feeding it.
No supply at a socket-outlet or point
A socket-outlet or point is dead — nothing plugged in works — while other points may be fine. A bread-and-butter 'trace it back' fault.