QualifiedMedium risk

Garden irrigation / pump controller not working

An irrigation controller or garden pump won't run the zones/pump — points at the controller power, the solenoids/pump supply, or wiring in a wet outdoor environment.

Safety first

Isolate before working. Outdoor/wet-area wiring and any mains pump must be on suitable, protected circuits. Low-voltage solenoid wiring is common but the supply side is mains.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Controller has no power / failed

    Most likely

    The controller's plugpack/supply is off or the controller has failed.

  2. 2

    Solenoid / zone wiring fault

    #2

    A broken/corroded solenoid wire or failed solenoid stops a zone.

  3. 3

    Pump supply / protection tripped

    #3

    A mains pump's circuit has tripped or lost supply.

  4. 4

    Programming / schedule issue

    Least likely

    The controller schedule, rain-sensor, or season setting stops it running.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 2
1

Confirm the controller has power and check its schedule/rain-sensor settings.

Expected reading

Controller powered; schedule active (no rain-sensor hold).

If it passes

Powered and set — check the solenoids/zones and pump supply.

If it fails

No power or schedule/rain hold — restore power / correct settings.

Mark this test
View all expected readings at once
1. Confirm the controller has power and check its schedule/rain-sensor settings.
Controller powered; schedule active (no rain-sensor hold).
2. Test a zone manually; check solenoid wiring and (for a mains pump) the pump's supply/protection.
Zones activate; pump has supply.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Irrigation/pump controller fault

    → step 2
  2. 2
    decision

    Is the controller powered and the schedule active (no rain hold)?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Do zones activate and (mains) pump have supply?

    Yes→ step 5No→ step 6
  4. 4
    result

    Restore power / correct schedule or rain-sensor settings.

  5. 5
    result

    If a specific zone fails, it's that solenoid/wiring.

  6. 6
    result

    Solenoid/zone wiring fault or pump supply tripped — rectify.

Common mistakes apprentices make

  • Overlooking a rain-sensor or seasonal-adjust hold.
  • Not checking the controller's plugpack/supply.
  • Ignoring corroded outdoor solenoid wiring.
  • Forgetting a mains pump is on its own protected circuit.

When to stop & escalate

Mains pump and supply-side work is licensed electrical. Low-voltage solenoid/controller wiring faults in wet areas should still be rectified to a suitable standard.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults