AdvancedHigh risk

High earth-fault loop impedance / earthing concern

Testing shows a high earth-fault loop impedance (or an earthing concern) on a circuit — meaning protection might not operate fast enough on a fault, which is a safety issue to resolve.

Safety first

A high loop impedance/poor earth can mean protection won't clear a fault quickly — a real shock/safety risk. This is licensed testing and rectification; follow your test procedures.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Poor earth/CPC connection on the circuit

    Most likely

    A loose, undersized, or broken protective-earth connection raises the loop impedance.

  2. 2

    Long run / undersized conductors

    #2

    A long circuit or undersized conductors increase impedance.

  3. 3

    Main earthing / bonding issue

    #3

    A problem at the main earth or bonding affects the loop.

  4. 4

    Loose connection adding resistance

    Least likely

    A high-resistance joint anywhere in the loop raises the reading.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 2
1

Re-test the loop impedance and check the protective-earth (CPC) continuity on the circuit per procedure.

Expected reading

Loop impedance and earth continuity within the values your procedure allows.

If it passes

If within limits, re-confirm the original reading/test method.

If it fails

Out of limits — trace the earth path and connections for the cause.

Mark this test
View all expected readings at once
1. Re-test the loop impedance and check the protective-earth (CPC) continuity on the circuit per procedure.
Loop impedance and earth continuity within the values your procedure allows.
2. Inspect the circuit's earth connections, the main earthing/bonding, and look for loose/high-resistance joints.
Sound, correctly-sized earth connections throughout.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    High loop impedance

    → step 2
  2. 2
    decision

    On re-test, is the loop/earth within allowed values?

    Yes→ step 3No→ step 4
  3. 3
    result

    Within limits — re-confirm the original reading/method.

  4. 4
    decision

    Are the earth connections/bonding sound and correctly sized?

    Yes→ step 5No→ step 6
  5. 5
    result

    Consider conductor sizing / run length.

  6. 6
    result

    Poor earth/bonding — rectify and re-test.

Common mistakes apprentices make

  • Treating a high loop reading as 'close enough'.
  • Not checking the main earthing/bonding.
  • Overlooking a loose earth connection.
  • Ignoring conductor sizing/run length.

When to stop & escalate

Earthing/loop-impedance issues are a safety matter and licensed work — rectify and re-test to confirm protection will operate correctly. Don't leave a circuit in service with a known earthing concern.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.