AdvancedHigh risk

Faint tingle or voltage on an appliance frame

A user reports a faint tingle off a stainless appliance, tap, or metal enclosure. A meter shows some voltage between the frame and true earth, but the RCD hasn't tripped.

Safety first

Touch voltage on metalwork is a serious shock hazard — treat it as dangerous and stop people using the equipment. Do not rely on 'it's only a tingle'. Isolate and investigate the earth path before anyone touches it again.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Lost or high-resistance protective earth

    Most likely

    If the earth to the frame is broken or high-resistance, normal leakage current can't drain away and lifts the frame to a touch voltage without drawing enough to trip protection.

  2. 2

    Accumulated leakage from electronics/filters

    #2

    EMC filters in many appliances leak a small current to the frame. With a poor earth, that leakage shows up as a touch voltage you can feel.

  3. 3

    Partial insulation breakdown inside the appliance

    #3

    A winding or element starting to break down to the frame puts voltage on the metalwork — a developing internal fault.

  4. 4

    Lost neutral raising local earth/MEN reference

    Least likely

    A neutral problem on the installation can shift earth references and energise metalwork — a wider and more dangerous fault than a single appliance.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Stop using the equipment. Safely isolate, then test continuity of the protective earth from the frame back to the main earth.

Expected reading

A low-resistance, solid earth connection to the frame.

If it passes

Earth path is intact — focus on insulation breakdown or wider neutral/earthing issues.

If it fails

A broken/high-resistance earth explains the touch voltage — repair the earth path before re-energising.

Mark this test
View all expected readings at once
1. Stop using the equipment. Safely isolate, then test continuity of the protective earth from the frame back to the main earth.
A low-resistance, solid earth connection to the frame.
2. With the appliance isolated and unplugged, insulation-resistance test active/neutral to the frame.
High insulation resistance between live parts and the frame.
3. Check neutral-to-earth at a nearby point and confirm the installation's main earthing/neutral is healthy.
Neutral-to-earth near zero and main earthing intact.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Tingle / voltage on appliance frame

    → step 2
  2. 2
    decision

    Is the protective earth to the frame solid and low-resistance?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is insulation resistance live-parts-to-frame high?

    Yes→ step 5No→ step 6
  4. 4
    result

    Broken / high-resistance earth — repair the earth path before re-energising.

  5. 5
    decision

    Is neutral-to-earth near zero and main earthing healthy?

    Yes→ step 7No→ step 8
  6. 6
    result

    Internal insulation breakdown — remove the appliance from service.

  7. 7
    result

    Local leakage with a marginal earth — confirm earthing and bonding.

  8. 8
    result

    Installation neutral/earthing fault — escalate urgently, keep equipment out of use.

Common mistakes apprentices make

  • Telling the customer the tingle is harmless and leaving the equipment in use.
  • Chasing the appliance when the real fault is a broken protective earth.
  • Not checking whether a lost neutral is energising metalwork more widely.
  • Re-energising before the earth path is proven solid.

When to stop & escalate

Touch voltage on metalwork combined with a neutral or main-earthing problem is a whole-of-installation hazard — escalate immediately and keep the equipment out of use. Stop if the fault extends beyond a single appliance.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.