Faint tingle or voltage on an appliance frame
A user reports a faint tingle off a stainless appliance, tap, or metal enclosure. A meter shows some voltage between the frame and true earth, but the RCD hasn't tripped.
Safety first
Touch voltage on metalwork is a serious shock hazard — treat it as dangerous and stop people using the equipment. Do not rely on 'it's only a tingle'. Isolate and investigate the earth path before anyone touches it again.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Lost or high-resistance protective earth
Most likelyIf the earth to the frame is broken or high-resistance, normal leakage current can't drain away and lifts the frame to a touch voltage without drawing enough to trip protection.
- 2
Accumulated leakage from electronics/filters
#2EMC filters in many appliances leak a small current to the frame. With a poor earth, that leakage shows up as a touch voltage you can feel.
- 3
Partial insulation breakdown inside the appliance
#3A winding or element starting to break down to the frame puts voltage on the metalwork — a developing internal fault.
- 4
Lost neutral raising local earth/MEN reference
Least likelyA neutral problem on the installation can shift earth references and energise metalwork — a wider and more dangerous fault than a single appliance.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeStop using the equipment. Safely isolate, then test continuity of the protective earth from the frame back to the main earth.
A low-resistance, solid earth connection to the frame.
Earth path is intact — focus on insulation breakdown or wider neutral/earthing issues.
A broken/high-resistance earth explains the touch voltage — repair the earth path before re-energising.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Tingle / voltage on appliance frame
→ step 2 - 2decision
Is the protective earth to the frame solid and low-resistance?
Yes→ step 3No→ step 4 - 3decision
Is insulation resistance live-parts-to-frame high?
Yes→ step 5No→ step 6 - 4result
Broken / high-resistance earth — repair the earth path before re-energising.
- 5decision
Is neutral-to-earth near zero and main earthing healthy?
Yes→ step 7No→ step 8 - 6result
Internal insulation breakdown — remove the appliance from service.
- 7result
Local leakage with a marginal earth — confirm earthing and bonding.
- 8result
Installation neutral/earthing fault — escalate urgently, keep equipment out of use.
Common mistakes apprentices make
- Telling the customer the tingle is harmless and leaving the equipment in use.
- Chasing the appliance when the real fault is a broken protective earth.
- Not checking whether a lost neutral is energising metalwork more widely.
- Re-energising before the earth path is proven solid.
When to stop & escalate
Touch voltage on metalwork combined with a neutral or main-earthing problem is a whole-of-installation hazard — escalate immediately and keep the equipment out of use. Stop if the fault extends beyond a single appliance.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
High earth-fault loop impedance / earthing concern
Testing shows a high earth-fault loop impedance (or an earthing concern) on a circuit — meaning protection might not operate fast enough on a fault, which is a safety issue to resolve.
Lost or high-resistance neutral
Strange symptoms across a circuit or installation — voltages going high and low on different loads, flickering, equipment damage — pointing to a lost or high-resistance neutral.
RCD / RCBO keeps tripping
An RCD or RCBO trips repeatedly — immediately on reset, randomly during the day, or only when certain equipment runs. The earth-leakage protection is doing its job; something is leaking.