QualifiedMedium risk

Air-con runs but isn't cooling (electrical checks)

The unit runs (fan blows) but doesn't cool — from an electrical standpoint, checking whether the compressor/outdoor unit is actually being commanded and powered before handing to refrigeration.

Safety first

Isolate before electrical checks. Cooling performance often involves refrigerant — that's refrigeration-tech territory; here we confirm the electrical side.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Outdoor unit/compressor not running

    Most likely

    The condenser/compressor isn't running, so no cooling — could be electrical (supply/contactor/cap) or refrigeration.

  2. 2

    Mode/setpoint wrong on the controller

    #2

    Set to fan-only, a too-high setpoint, or a schedule limiting it.

  3. 3

    Outdoor fan/contactor/capacitor fault

    #3

    A failed run capacitor, contactor, or outdoor fan motor stops the outdoor unit working.

  4. 4

    Refrigerant/mechanical issue (hand off)

    Least likely

    Low refrigerant or a mechanical fault — refrigeration tech required.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 2
1

Check the controller mode/setpoint/schedule is actually calling for cooling.

Expected reading

Cooling mode, setpoint below room temp, not schedule-limited.

If it passes

It's calling for cooling — check the outdoor unit electrically.

If it fails

Wrong mode/setpoint/schedule — correct it.

Mark this test
View all expected readings at once
1. Check the controller mode/setpoint/schedule is actually calling for cooling.
Cooling mode, setpoint below room temp, not schedule-limited.
2. Isolate and check the outdoor unit's supply, contactor, run capacitor, and fan when cooling is called.
Outdoor unit powered, contactor pulling in, fan running, capacitor healthy.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Aircon not cooling

    → step 2
  2. 2
    decision

    Is the controller actually calling for cooling?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the outdoor unit powered, commanded, and electrically healthy?

    Yes→ step 5No→ step 6
  4. 4
    result

    Correct mode/setpoint/schedule.

  5. 5
    result

    Electrically OK but not cooling — refrigeration technician.

  6. 6
    result

    Electrical fault (contactor/cap/fan/supply) — rectify.

Common mistakes apprentices make

  • Not checking the controller is actually in cooling mode.
  • Assuming refrigerant when a run capacitor/contactor has failed.
  • Attempting refrigerant work without a licence.
  • Not isolating before checking the outdoor unit.

When to stop & escalate

Once the electrical side is confirmed (unit powered and commanded), cooling-performance/refrigerant issues are for a licensed refrigeration technician.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.