Ducted air-con system has no power / won't start
A ducted system (roof/cupboard fan unit + zones/controller) is dead or won't start — pointing at the dedicated supply/isolator, the controller, zone motors, or the unit's PCB.
Safety first
Roof-space/cupboard units involve height/access and a dedicated supply — isolate and prove dead. Refrigeration internals need a refrigeration tech.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
- 1
Dedicated supply/isolator off or tripped
Most likelyThe ducted unit's dedicated circuit/isolator (often in the roof) is off/tripped.
- 2
Zone controller / wall controller fault
#2The controller has no power or has failed, so the system won't start.
- 3
Unit PCB / transformer fault
#3The unit's control board or its low-voltage control transformer has failed.
- 4
Safety/condensate switch tripped
Least likelyA condensate overflow or safety switch has shut the unit down.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Check the dedicated supply/isolator (often in the roof space) and confirm power at the unit.
Isolator on, circuit healthy, power at the unit.
Powered — check the controller and any safety/condensate switch.
Isolator off / tripped — restore (find why if tripped).
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Ducted system no power
→ step 2 - 2decision
Is the dedicated isolator on and power at the unit?
Yes→ step 3No→ step 4 - 3decision
Does the controller respond and are safety/condensate switches OK?
Yes→ step 5No→ step 6 - 4result
Restore isolator/circuit/supply.
- 5result
Suspect the unit transformer/PCB — rectify / qualified service.
- 6result
Dead controller or tripped safety/condensate — rectify.
Common mistakes apprentices make
- Forgetting the dedicated isolator is often up in the roof space.
- Overlooking a tripped condensate-overflow switch.
- Not checking the controller has power.
- Working at height without safe access.
When to stop & escalate
Electrical supply/controller/transformer work is licensed electrical; refrigeration internals need a refrigeration technician. Condensate/drainage issues may also involve mechanical work.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
Split-system air-con not running at all
A split-system (head unit + outdoor condenser) is completely dead — no response from the remote/controller — pointing at supply, isolator, controller, or the indoor PCB.
Air-con tripping the power
An air-con unit trips its breaker or safety switch — on start, when the compressor kicks in, or randomly — pointing at the compressor, an earth fault, or the supply/protection.
Air-con condensate pump not working / unit shut down on overflow
An aircon has shut down on a condensate overflow/float switch, or its condensate pump isn't running — water isn't being removed, so the unit stops to prevent overflow.