Split-system air-con not running at all
A split-system (head unit + outdoor condenser) is completely dead — no response from the remote/controller — pointing at supply, isolator, controller, or the indoor PCB.
Safety first
Isolate at the dedicated isolator and prove dead before working. Refrigeration/gas work is restricted to licensed refrigeration techs — this covers the electrical side only.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Full detail — causes, the why, and common mistakes.
Likely causes
Ranked from most to least likely.
- 1
No supply / isolator off / tripped
Most likelyThe dedicated aircon isolator is off, or the circuit has tripped.
- 2
Remote/controller fault or batteries
#2A dead remote or wall controller means no run command.
- 3
Indoor unit PCB / control fault
#3The indoor control board has failed.
- 4
Indoor-outdoor interconnect fault
Least likelyThe interconnecting control/power wiring between units is faulty.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
Check the dedicated isolator and circuit, and confirm supply at the indoor unit.
Isolator on, circuit healthy, supply present.
Powered — check the controller/remote and indoor PCB.
Isolator off / tripped / no supply — restore (find why if tripped).
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Split system dead
→ step 2 - 2decision
Is the isolator on, circuit healthy, supply present?
Yes→ step 3No→ step 4 - 3decision
Does the controller/remote respond and command a run?
Yes→ step 5No→ step 6 - 4result
Restore isolator/circuit/supply.
- 5result
Suspect interconnect or indoor PCB — rectify / qualified service.
- 6result
Dead remote/controller — batteries / rectify controller.
Common mistakes apprentices make
- Not checking the dedicated isolator (often a separate switch).
- Overlooking a dead remote/controller.
- Attempting refrigeration work without a refrigeration licence.
- Working without isolating at the unit.
When to stop & escalate
Electrical supply/isolator/controller work is licensed electrical; refrigeration faults and gas work need a licensed refrigeration technician. PCB faults usually need the manufacturer/qualified service.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Related faults
Air-con tripping the power
An air-con unit trips its breaker or safety switch — on start, when the compressor kicks in, or randomly — pointing at the compressor, an earth fault, or the supply/protection.
Air-con runs but isn't cooling (electrical checks)
The unit runs (fan blows) but doesn't cool — from an electrical standpoint, checking whether the compressor/outdoor unit is actually being commanded and powered before handing to refrigeration.
Ducted air-con system has no power / won't start
A ducted system (roof/cupboard fan unit + zones/controller) is dead or won't start — pointing at the dedicated supply/isolator, the controller, zone motors, or the unit's PCB.
Learn the theory
How the gear and circuits behind this fault actually work.