AdvancedHigh risk

RCD passes test but doesn't trip on a real leakage test

The RCD's own button trips it, but a proper instrument test shows it doesn't trip within the required time/current — so it may not protect adequately in a real fault.

Safety first

An RCD that doesn't trip within spec may not protect people from shock. Treat it as inadequate protection until corrected. RCD instrument testing must follow your procedure.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    RCD aged / mechanism slowing

    Most likely

    The RCD has aged and its trip time/current has drifted out of specification.

  2. 2

    Wrong RCD rating/type for the requirement

    #2

    An RCD of the wrong sensitivity or type doesn't meet the protection required.

  3. 3

    Wiring affecting the test

    #3

    Wiring issues (e.g. parallel paths, incorrect connections) affect measured trip performance.

  4. 4

    Test method/setup issue

    Least likely

    An incorrect test setup gives misleading results.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Verify the test setup and that the correct RCD type/rating is being tested to the right criteria.

Expected reading

Correct setup and criteria for the RCD type/rating.

If it passes

Setup correct — the result reflects the RCD's real performance.

If it fails

Setup/criteria wrong — correct and re-test.

Mark this test
View all expected readings at once
1. Verify the test setup and that the correct RCD type/rating is being tested to the right criteria.
Correct setup and criteria for the RCD type/rating.
2. Confirm the RCD wiring is correct and there are no parallel earth paths affecting the test.
Correct wiring; no parallel paths skewing results.
3. If the RCD genuinely tests out of spec, plan its replacement with a correctly rated/type device.
A compliant RCD that trips within spec after replacement.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    RCD out of spec on test

    → step 2
  2. 2
    decision

    Is the test setup/criteria correct for the RCD?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is wiring correct with no parallel earth paths?

    Yes→ step 5No→ step 6
  4. 4
    result

    Correct setup/criteria and re-test.

  5. 5
    result

    RCD genuinely out of spec — replace with a correct device and re-verify.

  6. 6
    result

    Wiring/parallel-path issue — correct it, then re-test.

Common mistakes apprentices make

  • Trusting only the test button and not a proper instrument test.
  • Wrong RCD type/rating for the protection required.
  • Parallel earth paths skewing the measured trip.
  • Leaving an out-of-spec RCD in service.

When to stop & escalate

RCD instrument testing and compliance are governed by the wiring rules and your procedures — an out-of-spec RCD should be replaced and re-verified by a qualified person. This is a safety matter.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.