QualifiedMedium risk

RCBO trips the instant you try to reset it

The RCBO won't stay set — push it up and it trips straight back down, with nothing switched on. Different behaviour from nuisance tripping under load.

Safety first

An instant trip with no load usually means a genuine standing fault on the circuit, not a faulty device. Don't keep slamming it up — isolate and test the circuit dead before re-energising.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Standing active-to-earth fault on the circuit

    Most likely

    A dead short or solid leakage from active to earth is present even with all loads off, so the RCBO sees the fault the instant it closes and trips immediately.

  2. 2

    Neutral-to-earth fault downstream

    #2

    A neutral touching earth past the RCBO unbalances it as soon as it's set — a classic 'trips on reset with nothing on' fault.

  3. 3

    Borrowed or crossed neutral with another circuit

    #3

    If this circuit's neutral is shared with another circuit's neutral, return current flows through the wrong path and the RCBO trips immediately.

  4. 4

    Failed RCBO mechanism

    Least likely

    Less common, but a device that trips with the circuit proven clear and disconnected may have failed internally.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Safely isolate, disconnect the circuit conductors from the RCBO's load side, and try to reset it with nothing connected.

Expected reading

With the load side disconnected, the RCBO should set and hold.

If it passes

Device holds with no load connected — the fault is on the circuit, not the RCBO.

If it fails

It still trips with the load side disconnected — the RCBO itself is suspect.

Mark this test
View all expected readings at once
1. Safely isolate, disconnect the circuit conductors from the RCBO's load side, and try to reset it with nothing connected.
With the load side disconnected, the RCBO should set and hold.
2. Dead-test the disconnected circuit: insulation resistance active-to-earth and neutral-to-earth.
High insulation resistance on both.
3. Check whether the neutral is shared/crossed with another circuit by comparing neutrals with the boards de-energised.
This circuit's neutral is independent and lands on the correct bar/terminal.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    RCBO trips instantly on reset

    → step 2
  2. 2
    decision

    Does it hold with the load side disconnected?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is insulation resistance to earth high on the dead circuit?

    Yes→ step 5No→ step 6
  4. 4
    result

    Fault is the RCBO itself — replace and retest.

  5. 5
    decision

    Is the neutral independent (not borrowed/crossed)?

    Yes→ step 7No→ step 8
  6. 6
    result

    Standing active/neutral-to-earth fault — split the circuit to locate it.

  7. 7
    result

    No circuit fault found — recheck device and terminations.

  8. 8
    result

    Borrowed/crossed neutral — correct the neutral arrangement.

Common mistakes apprentices make

  • Condemning the RCBO before disconnecting the load side to prove where the fault is.
  • Forgetting a neutral-to-earth fault trips an RCBO just as readily as an active fault.
  • Missing a shared/borrowed neutral between two circuits.
  • Repeatedly resetting onto a standing fault instead of testing dead.

When to stop & escalate

If the standing fault is in a buried or inaccessible cable, escalate for fault location rather than guessing. A borrowed neutral can indicate non-compliant past work across multiple circuits — flag it for proper rectification.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.