AdvancedHigh risk

Main switch / incomer not making on all phases

A board's main switch or incomer isn't passing all phases — downstream gets partial supply (single-phasing) or nothing — pointing at the switch contacts or its terminations.

Safety first

The supply side of a main switch/incomer is live even with it open. Isolate upstream where possible, prove dead, and treat as licensed, high-energy work.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Main switch pole not making

    Most likely

    One pole of the main switch isn't closing/conducting, dropping a phase downstream.

  2. 2

    Loose/burnt incomer termination

    #2

    A loose or burnt incoming/outgoing terminal on one phase opens or partially opens it.

  3. 3

    Upstream supply loss of a phase

    #3

    A phase is already missing on the supply side (service fuse/supply authority).

  4. 4

    Failed main switch

    Least likely

    The switch itself has failed mechanically/electrically.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Measure all three phases on the supply side and load side of the main switch.

Expected reading

Three phases present both sides when the switch is on.

If it passes

All phases pass — the loss is downstream; trace from the board.

If it fails

A phase present on supply side but missing on load side → the main switch/termination is the fault.

View all expected readings at once
1. Measure all three phases on the supply side and load side of the main switch.
Three phases present both sides when the switch is on.
2. If a phase is missing on the supply side too, check the incoming supply / service.
All three phases present on the supply side.
3. Isolate and inspect the switch poles and terminations for the dropped phase.
Clean, making pole and a sound termination.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Incomer not making all phases

    → step 2
  2. 2
    decision

    Are all three phases present on the load side of the main switch?

    Yes→ step 3No→ step 4
  3. 3
    result

    All phases pass — the loss is downstream; trace it.

  4. 4
    decision

    Are all three phases present on the supply side?

    Yes→ step 5No→ step 6
  5. 5
    result

    Switch pole/termination dropping a phase — rectify/replace.

  6. 6
    result

    Phase missing at supply — escalate upstream (service/authority).

Common mistakes apprentices make

  • Assuming a downstream fault when the main switch is dropping a phase.
  • Not measuring both sides of the switch.
  • Overlooking an upstream/service phase loss.
  • Working on the live supply side without proper isolation.

When to stop & escalate

Supply-side/service phase loss is the supply authority's domain. Main switch/incomer rectification is high-energy licensed work — isolate properly.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults