QualifiedMedium risk

Phase-failure / monitoring relay has tripped the circuit

A phase-failure or phase-sequence monitoring relay has dropped out and is holding the control circuit off, stopping the equipment — even though the panel looks powered.

Safety first

The monitoring relay is protecting the equipment from a supply problem. Don't bypass it to get running — find the supply fault it's detecting. Power can still be live on some phases.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Genuine phase loss or imbalance

    Most likely

    The relay has correctly detected a missing or unbalanced phase and dropped out to protect the load.

  2. 2

    Wrong phase sequence (after supply work)

    #2

    A phase-sequence relay trips if phases were swapped during supply work, protecting direction-sensitive equipment.

  3. 3

    Relay set too sensitively

    #3

    Imbalance/voltage thresholds set too tight cause nuisance trips on normal supply variation.

  4. 4

    Faulty monitoring relay

    Least likely

    The relay itself has failed and is dropping out with a healthy supply.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Measure the three phase-to-phase voltages at the relay's sensing terminals.

Expected reading

Three balanced phase-to-phase voltages present.

If it passes

Supply looks healthy — check sequence, settings, then the relay.

If it fails

A missing/unbalanced phase confirms why it tripped — chase the supply.

View all expected readings at once
1. Measure the three phase-to-phase voltages at the relay's sensing terminals.
Three balanced phase-to-phase voltages present.
2. If recent supply work was done, verify the phase sequence matches what the relay expects.
Correct phase sequence at the sensing terminals.
3. Check the relay's imbalance/voltage settings against the supply, and confirm it resets with a known-good supply.
Sensible settings and a clean reset on good supply.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Phase-monitor relay tripped

    → step 2
  2. 2
    decision

    Are all three phase-to-phase voltages balanced and present?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the phase sequence correct?

    Yes→ step 5No→ step 6
  4. 4
    result

    Missing/unbalanced phase — chase the supply fault (do not bypass).

  5. 5
    decision

    Are settings sensible and does it reset on good supply?

    Yes→ step 7No→ step 8
  6. 6
    result

    Reversed sequence — correct the connections.

  7. 7
    result

    Healthy — supply event may have been transient; monitor.

  8. 8
    result

    Over-tight settings or failed relay — adjust or replace.

Common mistakes apprentices make

  • Bypassing the monitoring relay to get running and exposing the load to single-phasing.
  • Not checking phase sequence after supply or transformer work.
  • Blaming the relay before confirming the supply is actually healthy.
  • Setting thresholds so tight that normal variation nuisance-trips it.

When to stop & escalate

A genuine phase loss or sequence problem at the supply is upstream — raise it appropriately rather than working around the relay. Never disable supply-protection to keep production running.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.