Intermittent dead or flickering load from a loose conductor
Lights or equipment on a circuit drop out, flicker, or come and go — sometimes with tapping, vibration, temperature, or load changes. The classic signature of a loose or partly-broken conductor.
Safety first
Loose/arcing connections generate heat and are a recognised fire risk. If you find heat or scorching, treat it seriously. Isolate before opening accessories, and don't keep tapping a live arcing joint to 'find' it.
Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.
Apprentice mode
Full walk-through — the why, what readings mean, mistakes & safety.
Likely causes
Ranked from most to least likely.
- 1
Loose terminal at an accessory or connection
Most likelyA conductor not properly clamped (or a back-stabbed termination) makes and breaks with vibration, temperature, or load, dropping the circuit intermittently and heating the joint.
- 2
Partly broken conductor strand
#2A nicked or fatigued conductor with only a few strands left carries load until it flexes or heats, then opens — common where cables flex or were over-bent.
- 3
High-resistance joint (corrosion / dissimilar metals)
#3Corrosion or a poor aluminium/copper joint raises resistance, causing voltage drop, heat, and intermittent operation as conditions change.
- 4
Loose connection at the switchboard
Least likelyA loose active/neutral at the breaker, neutral bar, or busbar drops everything downstream intermittently and can run dangerously hot.
Reports are saved on this device to reflect what you actually find.
Testing sequence
Work through one test at a time. Expected reading and what each result means.
On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.
Enter Job ModeMap exactly what's affected to find the common point (one fitting, one circuit, or everything past a board terminal).
A clear common point where the fault must sit.
The common point tells you where to concentrate the search.
If the pattern is unclear, monitor voltage at the load while provoking it (tap/load/heat) safely.
View all expected readings at once
Fault-finding flowchart
The same logic as a decision tree.
- 1start
Intermittent dead/flickering load
→ step 2 - 2decision
Do the affected loads share a common point?
Yes→ step 3No→ step 4 - 3decision
Are terminations at the common point / board sound?
Yes→ step 5No→ step 6 - 4result
Monitor voltage at the load while provoking it safely to find the common point.
- 5decision
Is conductor resistance low and consistent along the run?
Yes→ step 7No→ step 8 - 6result
Loose / heat-damaged termination — remake it and replace damaged parts.
- 7result
Re-examine every termination including the neutral path.
- 8result
Broken / high-resistance conductor — replace the affected section.
Common mistakes apprentices make
- Tightening one obvious terminal and assuming the intermittent fault is fixed.
- Overlooking the neutral side — a loose neutral causes the same symptoms.
- Not checking the switchboard terminations when several things drop together.
- Leaving a heat-damaged accessory in service after remaking the joint.
When to stop & escalate
Any sign of significant overheating or scorching means the connection (and possibly the cable) may be compromised — stop and investigate fully. Escalate if the broken conductor is in an inaccessible or concealed run that needs proper fault location.
If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.
Was this guide helpful?
Related faults
Loose connection overheating (discolouration / smell)
A terminal or connection is overheating — discoloured insulation, a burning smell, or heat you can feel — a common cause of nuisance faults and a real fire risk.
Intermittent fault that's hard to reproduce
Something fails occasionally — random trips, dropouts, or stoppages — but works fine when you go to look at it. The classic 'can't fault it on the bench' problem.
Lost or high-resistance neutral
Strange symptoms across a circuit or installation — voltages going high and low on different loads, flickering, equipment damage — pointing to a lost or high-resistance neutral.