AdvancedHigh risk

Commercial exhaust / ventilation fan not running

A larger exhaust/ventilation fan (carpark, kitchen, plant room) won't run — pointing at its starter/control, supply, motor, or an interlock with a control system.

Safety first

Larger fans are often three-phase on a starter and may be safety/ventilation-critical (e.g. carpark CO, kitchen exhaust). Isolate and prove dead; confirm the system's role before disabling anything.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Starter/control not energising the fan

    Most likely

    The fan's contactor/starter isn't being commanded (control circuit, overload, or interlock).

  2. 2

    Overload tripped / motor fault

    #2

    The fan's overload has tripped or the motor has a fault.

  3. 3

    Control-system interlock holding it off

    #3

    A BMS/CO/fire interlock is holding the fan off (possibly correctly).

  4. 4

    Supply / single-phasing

    Least likely

    Lost supply or a lost phase on a three-phase fan.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Check whether the fan's starter/contactor is being commanded and whether its overload has tripped.

Expected reading

Starter commanded; overload not tripped.

If it passes

Commanded — check the motor and supply.

If it fails

Not commanded / overload tripped — trace the control/overload (see motor faults).

Mark this test
View all expected readings at once
1. Check whether the fan's starter/contactor is being commanded and whether its overload has tripped.
Starter commanded; overload not tripped.
2. Confirm whether a control-system/safety interlock (BMS/CO/fire) is intentionally holding it off.
No interlock holding it (or a known, correct one).
3. Check the motor and three-phase supply (single-phasing) per the motor fault-finding.
Healthy motor and balanced three-phase supply.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Commercial fan not running

    → step 2
  2. 2
    decision

    Is the starter commanded and the overload not tripped?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is any safety/BMS interlock NOT holding it off?

    Yes→ step 5No→ step 6
  4. 4
    result

    Trace the control/overload (see motor fault-finding).

  5. 5
    decision

    Is the motor healthy and three-phase supply balanced?

    Yes→ step 7No→ step 8
  6. 6
    result

    An interlock holds it — confirm whether that's correct first.

  7. 7
    result

    Re-check the control/starter.

  8. 8
    result

    Motor fault or single-phasing — rectify.

Common mistakes apprentices make

  • Defeating a safety/ventilation interlock without understanding its role.
  • Not checking the overload.
  • Overlooking single-phasing on a three-phase fan.
  • Assuming the motor before checking the control/starter.

When to stop & escalate

Ventilation fans tied to safety systems (carpark CO, smoke/kitchen exhaust) must not be defeated — confirm the system design. Starter/motor/three-phase work is licensed electrical.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.