ApprenticeMedium risk

All lights in one area out (others fine)

Every light in one part of the house is dead while power points and other lighting still work — points at that lighting circuit's protective device or a shared fault.

Safety first

A tripped protective device is protecting against a fault — don't just keep resetting it. Isolate and prove dead before investigating fittings.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Lighting circuit breaker/RCBO tripped

    Most likely

    The protective device for that lighting circuit has tripped (overload, short, or earth fault).

  2. 2

    Fault on one fitting taking out the circuit

    #2

    A failed fitting or water ingress can trip the whole circuit's protection.

  3. 3

    Loose connection at a shared junction

    #3

    A loose neutral/active at a junction feeding that area kills everything downstream.

  4. 4

    Switch or controller feeding the area faulty

    Least likely

    A common switch or controller for the area has failed.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Check the switchboard: has the lighting circuit's breaker/RCBO tripped?

Expected reading

Protective device on; nothing tripped.

If it passes

Not tripped — trace the shared wiring/switch for that area.

If it fails

Tripped — find why before resetting (don't just re-trip it).

Mark this test
View all expected readings at once
1. Check the switchboard: has the lighting circuit's breaker/RCBO tripped?
Protective device on; nothing tripped.
2. If tripped, isolate suspect fittings (or split the circuit) and reset to find what trips it.
Circuit holds with the faulty fitting/section removed.
3. If not tripped, trace the shared junction/switch feeding the dead area for a loose/broken connection.
Sound connections and a working feed to the area.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    All lights one area out

    → step 2
  2. 2
    decision

    Has the lighting circuit's protective device tripped?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does isolating a fitting/section let it reset and hold?

    Yes→ step 5No→ step 6
  4. 4
    result

    Not tripped — trace the shared junction/switch for that area.

  5. 5
    result

    The item that re-trips it is the fault — repair it.

  6. 6
    result

    Trips with all off — fault is in the fixed wiring.

Common mistakes apprentices make

  • Repeatedly resetting a tripping breaker instead of finding the fault.
  • Not isolating fittings to localise what's tripping the circuit.
  • Overlooking water ingress in an outdoor/bathroom fitting on the circuit.
  • Missing a loose neutral at a shared junction.

When to stop & escalate

Fixed-wiring faults and anything causing repeated tripping must be found and repaired by a licensed electrician before re-energising. Never defeat or upsize the protection to stop the tripping.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.