Motor noisy or whining when run on a VSD

The motor runs but is noticeably noisy on the drive — a whine, whistle, or growl that isn't there on direct supply, sometimes worse at certain speeds.

Safety first

Mostly a quality/comfort issue, but persistent resonance can stress the drivetrain. Isolate before mechanical checks. Keep clear of the shaft.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Switching (carrier) frequency audible

    Most likely

    A low carrier frequency makes the motor emit an audible whine that a higher carrier can reduce.

  2. 2

    Mechanical resonance at certain speeds

    #2

    The system resonates at particular frequencies, producing noise/vibration at those speeds.

  3. 3

    Control mode / tuning

    #3

    Some control modes or aggressive tuning create more audible noise.

  4. 4

    Genuine mechanical issue surfacing

    Least likely

    Bearings/coupling problems can be more apparent under drive operation.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Note whether the noise changes with speed and whether it's a steady whine or speed-specific.

Expected reading

A characterisation: steady whine vs speed-specific resonance.

If it passes

Steady whine → likely carrier frequency. Speed-specific → resonance.

If it fails

Noise that tracks a mechanical fault → check bearings/coupling.

Mark this test
View all expected readings at once
1. Note whether the noise changes with speed and whether it's a steady whine or speed-specific.
A characterisation: steady whine vs speed-specific resonance.
2. For a steady whine, try adjusting the carrier/switching frequency per the drive's range.
Whine reduces with a suitable carrier frequency.
3. For speed-specific noise, identify the speed(s); consider skip frequencies. For mechanical noise, check bearings/coupling.
Resonance avoided via skip frequencies, or a mechanical issue found.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Motor noisy on VSD

    → step 2
  2. 2
    decision

    Is it a steady whine (vs speed-specific or mechanical)?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does adjusting carrier frequency reduce it?

    Yes→ step 5No→ step 4
  4. 4
    decision

    Is it tied to specific speeds (resonance)?

    Yes→ step 6No→ step 7
  5. 5
    result

    Carrier-frequency whine — set within the allowed range.

  6. 6
    result

    Use skip frequencies to avoid the resonant point.

  7. 7
    result

    Mechanical fault surfacing — check bearings/coupling.

Common mistakes apprentices make

  • Assuming a fault when it's just audible carrier-frequency whine.
  • Raising carrier frequency without regard to drive derating/heat.
  • Not using skip frequencies for a clear resonance point.
  • Missing a genuine bearing problem made obvious by the drive.

When to stop & escalate

Carrier-frequency changes can affect drive heating and cable stress — stay within the manufacturer's guidance. Persistent resonance may need a mechanical/structural review.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?