QualifiedLow risk

Timer behaving as the wrong type (on-delay vs off-delay)

The timer switches at the wrong point in the sequence because it's acting as the wrong function — on-delay where off-delay is needed, single-shot where cyclic is needed, and so on.

Safety first

A timer in the wrong mode can energise or hold equipment unexpectedly. Confirm the intended behaviour is safe before and after changing the mode.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Function/mode selector set wrong

    Most likely

    Multi-function timers have a mode selector; the wrong selection gives on-delay vs off-delay vs interval behaviour.

  2. 2

    Wrong timer type fitted

    #2

    A fixed-function timer of the wrong type was installed for the application.

  3. 3

    Trigger/supply wiring matched to a different mode

    Least likely

    Some modes need the supply/trigger wired differently; mismatched wiring gives unexpected behaviour.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Confirm what behaviour the sequence needs (on-delay, off-delay, interval, cyclic).

Expected reading

A clear required behaviour.

If it passes

Requirement clear — check the mode selector against it.

If it fails

If unclear, confirm the intended behaviour from the control description.

Mark this test
View all expected readings at once
1. Confirm what behaviour the sequence needs (on-delay, off-delay, interval, cyclic).
A clear required behaviour.
2. Check the timer's mode/function selector matches the required behaviour.
Mode selector set to the needed function.
3. Confirm the supply/trigger wiring suits the selected mode per the timer's diagram.
Wiring matches the selected mode.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Timer wrong mode

    → step 2
  2. 2
    decision

    Is the required behaviour (on/off-delay/interval) clear?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Does the mode selector match the requirement?

    Yes→ step 5No→ step 6
  4. 4
    result

    Confirm intended behaviour from the control description.

  5. 5
    decision

    Does the supply/trigger wiring suit that mode?

    Yes→ step 7No→ step 8
  6. 6
    result

    Set the correct mode (or fit the right fixed-function type).

  7. 7
    result

    Re-test the sequence.

  8. 8
    result

    Rewire per the timer's diagram for that mode.

Common mistakes apprentices make

  • Not checking the multi-function mode selector.
  • Fitting a fixed-function timer of the wrong type.
  • Wiring the supply/trigger for a different mode than selected.
  • Changing the mode without confirming the intended behaviour.

When to stop & escalate

If the intended timing behaviour isn't documented, confirm it against the control description before changing the mode, especially where it affects start/stop sequencing.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.