QualifiedMedium risk

Motor trips protection on start but runs fine if it gets going

Protection trips during the start/inrush, but on the rare occasion it gets running it's fine — pointing at starting current, settings, or load inertia rather than a running fault.

Safety first

Repeated start attempts heat the motor and stress the supply. Limit attempts. The motor may start unexpectedly when protection is reset.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Protection too sensitive for the inrush

    Most likely

    A breaker/overload with the wrong trip characteristic or setting trips on normal starting current.

  2. 2

    High load inertia / hard start

    #2

    A high-inertia or loaded start draws heavy current for longer, tripping time-limited protection.

  3. 3

    Star-delta / starter not reducing starting current

    #3

    A reduced-voltage starter that isn't working (e.g. stuck in delta or failed star) lets full inrush through.

  4. 4

    Weak supply sagging on start

    Least likely

    A weak supply that dips on inrush can cause protection or drive faults at start.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Identify which device trips and its type/setting; compare to the motor's starting requirements.

Expected reading

Protection rated/charactered to ride through normal starting.

If it passes

Protection suits the motor — look at load inertia and the starter.

If it fails

Wrong characteristic/setting — select protection suited to the start.

View all expected readings at once
1. Identify which device trips and its type/setting; compare to the motor's starting requirements.
Protection rated/charactered to ride through normal starting.
2. For reduced-voltage starters, confirm they actually reduce starting current (star engages, soft-start ramps).
The starter limits inrush as designed during start.
3. Clamp starting current and watch supply voltage during the attempt; assess the load inertia.
Starting current/time within what protection allows; supply holds.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Trips on start only

    → step 2
  2. 2
    decision

    Is the protection's characteristic/setting suited to starting?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the reduced-voltage starter actually limiting inrush?

    Yes→ step 5No→ step 6
  4. 4
    result

    Wrong characteristic/setting — select suitable protection.

  5. 5
    decision

    Are starting current/time and supply within limits?

    Yes→ step 7No→ step 8
  6. 6
    result

    Starter not reducing inrush — repair it.

  7. 7
    result

    Within limits — investigate intermittent protection behaviour.

  8. 8
    result

    Excess inrush or supply sag — address load/supply.

Common mistakes apprentices make

  • Upsizing protection to stop the trips instead of fixing the start.
  • Not realising a reduced-voltage starter has stopped working.
  • Ignoring a supply that sags badly on inrush.
  • Repeatedly slamming start and overheating the motor.

When to stop & escalate

If the start genuinely needs more than the supply/protection can give, the starting method or supply should be reviewed at design level rather than defeating protection.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults

Learn the theory

How the gear and circuits behind this fault actually work.