ApprenticeHigh risk

Immersion / tank heater not working

An immersion or tank heater isn't heating the water/fluid — it stays cold despite the thermostat calling, or trips its protection.

Safety first

Immersion heaters combine water and electricity — earth-leakage and shock risk if the element fails. Isolate, prove dead, and never bypass earth-leakage protection. Hot water scald risk.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Thermostat tripped or set low / faulty

    Most likely

    The control thermostat (or a tripped high-limit cut-out) is stopping the element, or the setpoint is too low.

  2. 2

    Open (burnt-out) element

    #2

    The immersion element has failed open and draws no current.

  3. 3

    No supply / blown fuse / tripped protection

    #3

    Lost supply, a blown fuse, or tripped breaker/RCD removes power.

  4. 4

    Element leaking to earth (tripping protection)

    Least likely

    A failing element leaks to earth and trips the RCD/breaker.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Check the thermostat/high-limit: is it calling for heat and not tripped, with a sensible setpoint?

Expected reading

Thermostat calling for heat; high-limit not tripped.

If it passes

Heat is called — check supply and the element.

If it fails

Setpoint low or cut-out tripped — adjust/reset (find why a cut-out tripped).

Mark this test
View all expected readings at once
1. Check the thermostat/high-limit: is it calling for heat and not tripped, with a sensible setpoint?
Thermostat calling for heat; high-limit not tripped.
2. Confirm supply to the heater (fuse/breaker/RCD on) when heat is called.
Supply present at the heater.
3. Isolate and test the element: resistance (open?) and insulation to earth.
Sensible element resistance and high insulation to earth.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Immersion heater not heating

    → step 2
  2. 2
    decision

    Is the thermostat calling and the high-limit not tripped?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is supply present at the heater?

    Yes→ step 5No→ step 6
  4. 4
    result

    Adjust setpoint / reset cut-out (find why it tripped).

  5. 5
    decision

    Is the element resistance sensible and insulation good?

    Yes→ step 7No→ step 8
  6. 6
    result

    Lost supply / tripped protection — find why before restoring.

  7. 7
    result

    Element healthy — re-check thermostat/control.

  8. 8
    result

    Open element or low insulation — replace the element.

Common mistakes apprentices make

  • Resetting a high-limit cut-out without finding why it tripped.
  • Bypassing the RCD when a leaking element trips it.
  • Not testing the element's insulation to earth.
  • Assuming the element when the thermostat is the issue.

When to stop & escalate

A leaking element is a replacement — never run it on defeated protection. A repeatedly tripping high-limit indicates a control fault to find before resetting.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults