QualifiedMedium risk

Contactor pulls in on the button but won't seal in

Press start and the contactor pulls in, but it drops out the moment you release the button. It won't latch/hold itself in through the seal-in circuit.

Safety first

You'll be working in a live control circuit near the start/stop station. Confirm what's isolated, treat the power side as live, and follow the machine's control drawings rather than guessing the logic.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Apprentice mode

Full walk-through — the why, what readings mean, mistakes & safety.

Likely causes

Ranked from most to least likely.

  1. 1

    Seal-in / hold-in auxiliary contact not making

    Most likely

    The normally-open auxiliary contact that parallels the start button (the seal-in) isn't closing or is high-resistance, so the coil loses its feed the instant the button is released.

  2. 2

    Wrong auxiliary used for the seal-in

    #2

    If the seal-in is wired through a normally-closed or the wrong auxiliary, the hold path never completes — common after a contactor or aux block swap.

  3. 3

    Open stop button / series safety contact

    #3

    A stop button, E-stop, or overload contact that's marginal can carry the brief push but open under the seal-in path, dropping the hold.

  4. 4

    Loose terminal in the seal-in branch

    Least likely

    A loose connection in the hold-in wiring makes the path while you press (through the button) but not through the auxiliary alone.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

On the tools? Job Mode shows one test at a time with thumb-sized buttons — your place and readings carry straight over.

Enter Job Mode
Test 1 of 3
1

Trace the control drawing and identify the seal-in auxiliary that parallels the start button.

Expected reading

A clearly identified NO auxiliary intended to hold the coil in.

If it passes

You know which contact must make — test it next.

If it fails

If the drawing shows no seal-in or the wrong contact type, the logic/wiring is the fault.

Mark this test
View all expected readings at once
1. Trace the control drawing and identify the seal-in auxiliary that parallels the start button.
A clearly identified NO auxiliary intended to hold the coil in.
2. Safely measure across the seal-in auxiliary while the contactor is energised (button held), checking it closes.
Near-zero volts across the auxiliary when the contactor is in (contact made).
3. With the button released, check continuity of the hold path through the stop button, overload, and series contacts (isolated and dead where required).
Continuous hold path through all series contacts.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Pulls in on button, won't seal in

    → step 2
  2. 2
    decision

    Does the seal-in auxiliary actually close when energised?

    Yes→ step 3No→ step 4
  3. 3
    decision

    Is the hold path continuous through stop/overload/series contacts?

    Yes→ step 5No→ step 6
  4. 4
    result

    Seal-in auxiliary not making / wrong contact — replace/adjust or rewire to the correct NO aux.

  5. 5
    result

    Recheck the auxiliary wiring and terminations in the seal-in branch.

  6. 6
    result

    Open stop/overload/series contact or loose terminal — repair the hold path.

Common mistakes apprentices make

  • Wiring the seal-in through the wrong auxiliary after swapping the contactor.
  • Assuming the coil is faulty when it pulls in fine — the fault is the hold path.
  • Not realising a marginal stop/overload contact only fails on the seal-in path.
  • Holding the button to 'make it work' and shipping it like that.

When to stop & escalate

If the seal-in passes through a safety contact (E-stop/overload) that's intermittently opening, stop and treat the safety circuit as the priority — don't bypass it to get the hold working. Escalate if the control logic doesn't match the drawings.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Was this guide helpful?

Related faults