ApprenticeMedium risk

Band / cartridge heater burnt out or underperforming

A band or cartridge heater (e.g. on a barrel or die) isn't reaching temperature or has failed — one zone stays cold or lags while others are fine.

Safety first

Band/cartridge heaters operate at high temperatures. Prove dead and allow cooling before handling. Confirm the correct zone is isolated.

Isolate, lock out / tag out, and prove dead before working unless a live test is specifically required, authorised, and carried out under proper supervision. Always follow local regulations, your site procedures, and the equipment manufacturer's documentation.

Full detail — causes, the why, and common mistakes.

Likely causes

Ranked from most to least likely.

  1. 1

    Open / burnt-out heater

    Most likely

    The band/cartridge element has failed open and draws no current.

  2. 2

    Poor contact / loose fit to the surface

    #2

    A band heater not clamped tightly, or a cartridge in a worn bore, transfers heat poorly and lags.

  3. 3

    Degraded element (partial)

    #3

    The element has risen in resistance and draws less current, so the zone underperforms.

  4. 4

    Connection / lead failure

    #4

    The heater's leads or terminations have failed where they flex or get hot.

  5. 5

    Zone switching/control fault

    Least likely

    The SSR/contactor or controller for that zone isn't driving the heater.

Reports are saved on this device to reflect what you actually find.

Testing sequence

Work through one test at a time. Expected reading and what each result means.

Test 1 of 3
1

Compare the affected zone's current/behaviour to a known-good zone while heat is called.

Expected reading

Similar current/heat-up to a healthy zone.

If it passes

Draws like a good zone but lags — suspect poor contact/fit.

If it fails

Low/no current — check switching, then the element/leads.

View all expected readings at once
1. Compare the affected zone's current/behaviour to a known-good zone while heat is called.
Similar current/heat-up to a healthy zone.
2. Confirm the zone's switching device is driving it; then isolate and measure the heater's resistance.
Switching active; sensible heater resistance.
3. Check the heater's fit/clamping and the condition of its leads/terminations.
Tight fit and sound leads/terminations.

Fault-finding flowchart

The same logic as a decision tree.

  1. 1
    start

    Band/cartridge zone cold

    → step 2
  2. 2
    decision

    Does the zone draw current like a good zone?

    Yes→ step 3No→ step 4
  3. 3
    result

    Draws fine but lags — check fit/clamping and leads.

  4. 4
    decision

    Is the zone's switching device driving it?

    Yes→ step 5No→ step 6
  5. 5
    result

    Element open/high — replace the heater.

  6. 6
    result

    Switching/control fault for that zone — address it.

Common mistakes apprentices make

  • Not comparing against a known-good zone.
  • Missing a loosely-clamped band heater that heats poorly.
  • Overlooking lead/termination failure where they flex or get hot.
  • Assuming the element when the zone's SSR/control is at fault.

When to stop & escalate

Repeated failures in one zone suggest a fit, rating, or control problem to address rather than just swapping heaters. Process-temperature impacts may involve production.

If you're past your competence, authorisation, or the safe limits of the job — stop and hand it on. There's no fault worth getting hurt over.

Related faults